2006-04-07 00:00:00 | DENIED |
| |
| 1)A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) PLEASE CLARIFY THE SCOPE OF WORK. |
| VERIFY THAT OFFICES 1, 2 AND 3 ARE |
| EXISTING AND HAVE EXISTING FOUNDATIONS. |
| |
| 3) SPECIFY THE CODE EDITION, |
| CONSTRUCTION TYPE AND TYPE OF OCCUPANCY. |
| INDICATE IF THE AREA IS FIRE |
| SPRINKLERED. |
| |
| 4) SPECIFY THE WIND DESIGN DATA, SUCH AS |
| WIND SPEED, IMPORTANCE FACTOR, ETC. SEE |
| 2004 FBC 1603.1.4. |
| |
| 5) SHOW COMPLIANCE WITH 2004 |
| FBC(EXISTING BUILDINGS) FOR LEVEL 2 |
| ALTERATIONS. SEE SECTIONS 601 THRU 611. |
| |
| 6) SPECIFY INTERIOR FINISH FLAME SPREAD |
| AND FIRE RESISTANCE. |
| |
| 7) FBC 1805.2 REQUIRES FOOTINGS TO HAVE |
| A MINIMUM DEPTH OF 12". CLARIFY THAT |
| ITEM #4 FOR NEW RAISED CONCRETE FLOOR IS |
| POURED OVER AN EXISTING FOUNDATION. |
| |
| 8) SPECIFY THE FASTENING FOR THE PLYWOOD |
| TO THE NEW 2X8 JOISTS. SEE FBC TABLE |
| 2304.9.1. (6"OC EDGES & INTERMEDIATE AND |
| 4"OC IN ZONE 3). |
| |
| 9) PROVIDE A WINDOW AND DOOR BUCK |
| DETAIL/FRAMING DETAIL FOR WINDOW AND |
| DOOR OPENINGS. |
| |
| 10) SPECIFY THE R-VALUE FOR WALL AND |
| CEILING INSULATION. COMPLY WITH FBC |
| CHAPTER 13. |
| |
| 11) SPECIFY THE ROOF COVERING AND SUBMIT |
| FL PRODUCT APPROVALS FOR ROOFING. |
| |
| 12) INDICATE HOW THE ACCESSIBLE ROUTE |
| WILL BE MAINTAINED FROM THE EXTERIOR |
| INTO OFFICE 1 AND FROM BOTH EXTERIOR AND |
| INTERIOR INTO OFFICE TWO WHEN THE CONC. |
| FLOORS ARE RAISED. SEE FBC 11-4.1.6. |
| |
| 13) SUBMIT FL PRODUCT APPROVALS FOR THE |
| SIMPSON CONNECTORS. |
| |
| 14) CITY OF WPB AMENDMENTS TO FBC |
| 106.3.3 REQUIRES THOSE PRODUCTS WHICH |
| ARE REGULATED BY DCA RULE 9B-72 TO BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL. |
| |
| 15) SPECIFY THE POSITIVE AND NEGATIVE |
| WINDLOAD PRESSURES AT THE EXTERIOR |
| OPENINGS FOR THE NEW WINDOWS AND DOORS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |