Plan Review Notes
Plan Review Notes For Permit 06031215
Permit Number 06031215
Review Stop B
Sequence Number 1
Notes
Date Text
2006-04-07 00:00:00DENIED
  
 1) SUBMIT PROJECT SPECIFICATIONS AND
 MATERIAL TAKE OFF TO VERIFY FLAME
 SPREAD, FIRE RESISTANCE AND ENERGY CODE
 COMPLIANCE. 2004 FBC(EXISTING BUILDINGS)
 SECTIONS 501, 503 AND 504.
  
 2) SPECIFY THE REQUIRED FIRE RESISTANCE
 RATING FOR THE TENANT SEPARATION WALLS
 AND THE APPROVED ASSEMBLY NUMBER. SEE
 FBC 708.
  
 3) SPECIFY THE TYPE AND R-VALUES OF THE
 INSULATION AND INDICATE WHERE EACH WILL
 BE INSTALLED. INDICATE IF ROOF/CEILING
 ASSEMBLY HAS AN ATTIC OR IS SINGLE
 ASSEMBLY. SEE FBC CHAPTER 13.
  
 4) SPECIFY THE FLAME SPREAD CLASS FOR
 THE INTERIOR FINISHES. SEE FBC 803.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved