Plan Review Notes
Plan Review Notes For Permit 06031214
Permit Number 06031214
Review Stop B
Sequence Number 1
Notes
Date Text
2006-04-07 00:00:00DENIED
  
 1) SUBMIT PROJECT SPECIFICATIONS AND
 MATERIAL TAKE OFF TO VERIFY FLAME
 SPREAD, FIRE RESISTANCE AND ENERGY CODE
 COMPLIANCE. 2004 FBC(EXISTING BUILDINGS)
 SECTIONS 501, 503 AND 504.
  
 2) SPECIFY THE REQUIRED FIRE RESISTANCE
 RATING FOR THE CEILING ASSEMBLY (IF
 REQUIRED)AND THE APPROVED ASSEMBLY
 NUMBER. SEE FBC 708.
  
 3) SPECIFY THE TYPE AND R-VALUES OF THE
 INSULATION. INDICATE IF ROOF/CEILING
 ASSEMBLY HAS AN ATTIC OR IS SINGLE
 ASSEMBLY. SEE FBC CHAPTER 13.
  
 4) SPECIFY THE FLAME SPREAD CLASS FOR
 THE INTERIOR FINISHES. SEE FBC 803.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714