Plan Review Notes For Permit 06031214 |
Permit Number |
06031214 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-04-07 00:00:00 | DENIED | | | | 1) SUBMIT PROJECT SPECIFICATIONS AND | | MATERIAL TAKE OFF TO VERIFY FLAME | | SPREAD, FIRE RESISTANCE AND ENERGY CODE | | COMPLIANCE. 2004 FBC(EXISTING BUILDINGS) | | SECTIONS 501, 503 AND 504. | | | | 2) SPECIFY THE REQUIRED FIRE RESISTANCE | | RATING FOR THE CEILING ASSEMBLY (IF | | REQUIRED)AND THE APPROVED ASSEMBLY | | NUMBER. SEE FBC 708. | | | | 3) SPECIFY THE TYPE AND R-VALUES OF THE | | INSULATION. INDICATE IF ROOF/CEILING | | ASSEMBLY HAS AN ATTIC OR IS SINGLE | | ASSEMBLY. SEE FBC CHAPTER 13. | | | | 4) SPECIFY THE FLAME SPREAD CLASS FOR | | THE INTERIOR FINISHES. SEE FBC 803. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|