2006-03-27 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 MYRON JACOBS(561) 805 6726
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2004
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) FBC TABLE 1609.6B.THE SYSTEM
 SELECTED FROM THE SUBMITTED FLAT ROOF
 PRODUCT APPROVAL NOA HAS A MAXIMUM
 DESIGN PRESSURE OF LESS THAN -89 PSF AND
 CITES GENERAL LIMITATION #9. GENERAL
 LIMITATION #9 PROHIBITS RATIONAL
 ANALYSIS OR EXTRAPOLATION TO ENHANCE THE
 UPLIFT PRESSURE AT PERIMETER AND CORNER
 AREAS BY REDUCING THE FASTENER SPACING
 IN THESE AREAS.EITHER SELECT AN
 ALTERNATIVE SYSTEM (OR PRODUCT APPROVAL)
 THAT DOES NOT CITE GENERAL LIMITATION
 #9.ALTERNATIVELY IF THE SELECTED
 SYSTEM DOES CITE GENERAL LIMITATION #9,
 IT MUST HAVE A MAXIMUM DESIGN PRESSURE
 THAT EXCEEDS THE PRESSURE IN ROOF ZONE 3
 (TYPICALLY -89 PSF FOR MEAN ROOF HEIGHT
 OF 30 FEET OR LESS). WHEN SUBMITTING
 PRODUCT APPROVALS FOR 'BUILT UP OR
 MODIFIED ROOFS, HI-LIGHT ORCIRCLE
 WHICH ASSEMBY WILL BE USED. BE AWARE OF
 THE GENERAL LIMITATION #7 WHICH
 SOMETIMES REQUIRES CALCULATIONS PREPARED
 BY A FLORIDA REGISTERED PROFESSIONAL
 SIGNED AND SEALED.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726