2006-03-27 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| MYRON JACOBS(561) 805 6726 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2004 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| F.S.= FLORIDA (STATE) STATUTE |
| |
| 1) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT BEFORE A |
| PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. |
| |
| 2) FBC TABLE 1609.6B.THE SYSTEM |
| SELECTED FROM THE SUBMITTED FLAT ROOF |
| PRODUCT APPROVAL NOA HAS A MAXIMUM |
| DESIGN PRESSURE OF LESS THAN -89 PSF AND |
| CITES GENERAL LIMITATION #9. GENERAL |
| LIMITATION #9 PROHIBITS RATIONAL |
| ANALYSIS OR EXTRAPOLATION TO ENHANCE THE |
| UPLIFT PRESSURE AT PERIMETER AND CORNER |
| AREAS BY REDUCING THE FASTENER SPACING |
| IN THESE AREAS.EITHER SELECT AN |
| ALTERNATIVE SYSTEM (OR PRODUCT APPROVAL) |
| THAT DOES NOT CITE GENERAL LIMITATION |
| #9.ALTERNATIVELY IF THE SELECTED |
| SYSTEM DOES CITE GENERAL LIMITATION #9, |
| IT MUST HAVE A MAXIMUM DESIGN PRESSURE |
| THAT EXCEEDS THE PRESSURE IN ROOF ZONE 3 |
| (TYPICALLY -89 PSF FOR MEAN ROOF HEIGHT |
| OF 30 FEET OR LESS). WHEN SUBMITTING |
| PRODUCT APPROVALS FOR 'BUILT UP OR |
| MODIFIED ROOFS, HI-LIGHT ORCIRCLE |
| WHICH ASSEMBY WILL BE USED. BE AWARE OF |
| THE GENERAL LIMITATION #7 WHICH |
| SOMETIMES REQUIRES CALCULATIONS PREPARED |
| BY A FLORIDA REGISTERED PROFESSIONAL |
| SIGNED AND SEALED. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| TEL:(561)805-6726 |