2006-08-24 00:00:00 | ******REVISION DENIED****** |
| REFERENCE: FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| |
| THE FOLLOWING INFORMATION IS REQUIRED |
| FOR GAS PLAN REVIEW FOR THE SUBMITTED |
| REVISION: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. (NOTE: PLEASE INCLUDE |
| ABOVE GROUND PIPE MEASUREMENTS AS WELL |
| AS THE UNDERGROUND PIPE MEASUREMENTS ON |
| THE REVISION.) |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| (NOTE: PLEASE INCLUDE ABOVE GROUND PIPE |
| MATERIAL AS WELL AS UNDERGROUND PIPE |
| MATERIAL ON THE REVISION.) |
| |
| 3. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| |
| 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING (ISOMETRIC) SHALL CLEARLY |
| PRINT AND SIGN NAME, AND ALSO DATE |
| DRAWING. PLEASE DO THIS PRIOR TO |
| RESUBMITTING. |
| |
| 5. PER FBC-2004, CHAPTER 1, SECTION |
| 106.1 SUBMITTAL DOCUMENTS. IF THE DESIGN |
| PROFESSIONAL IS AN ARCHITECT LEGALLY |
| REGISTERED UNDER THE LAWS OF THIS STATE |
| REGULATING THE PRACTICE OF ARCHITECTURE |
| AS PROVIDED FOR IN CHAPTER 481, FLORIDA |
| STATUTES, PART 1, FLORIDA STATUTES, THEN |
| HE OR SHE SHALL AFFIX HIS OR HER SEAL, |
| SIGNATURE AND DATE TO SAID DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA, AS |
| REQUIRED BY FLORIDA STATUTES. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| UNDER SUPERVISION OF K.STEVENS |
| (561) 805-6721 |
| |
| |
| |
| |
| |
| |
| |