2006-08-24 00:00:00******REVISION DENIED******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PLAN REVIEW FOR THE SUBMITTED
 REVISION:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. (NOTE: PLEASE INCLUDE
 ABOVE GROUND PIPE MEASUREMENTS AS WELL
 AS THE UNDERGROUND PIPE MEASUREMENTS ON
 THE REVISION.)
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 (NOTE: PLEASE INCLUDE ABOVE GROUND PIPE
 MATERIAL AS WELL AS UNDERGROUND PIPE
 MATERIAL ON THE REVISION.)
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING (ISOMETRIC) SHALL CLEARLY
 PRINT AND SIGN NAME, AND ALSO DATE
 DRAWING. PLEASE DO THIS PRIOR TO
 RESUBMITTING.
  
 5. PER FBC-2004, CHAPTER 1, SECTION
 106.1 SUBMITTAL DOCUMENTS. IF THE DESIGN
 PROFESSIONAL IS AN ARCHITECT LEGALLY
 REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE
 AS PROVIDED FOR IN CHAPTER 481, FLORIDA
 STATUTES, PART 1, FLORIDA STATUTES, THEN
 HE OR SHE SHALL AFFIX HIS OR HER SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA, AS
 REQUIRED BY FLORIDA STATUTES.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  