Plan Review Notes
Plan Review Notes For Permit 06031034
Permit Number 06031034
Review Stop B
Sequence Number 1
Notes
Date Text
2006-03-22 00:00:00DENIED
  
 1) THE DESIGN PRESSURE FOR THE POLYGLASS
 MODIFIED BITUMEN SYSTEM IS TOO LOW AND
 REQUIRES ENHANCED FASTENING. LIMITATION
 NUMBER 7 ON PAGE 45 OF THE NOA REQUIRES
 THAT THESE CALCULATIONS ARE DONE BY AN
 ENGINEER OR ARCHITECT. SUBMIT SIGNED AND
 SEALED CALCULATIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  