Plan Review Notes For Permit 06031034 |
Permit Number |
06031034 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-03-22 00:00:00 | DENIED | | | | 1) THE DESIGN PRESSURE FOR THE POLYGLASS | | MODIFIED BITUMEN SYSTEM IS TOO LOW AND | | REQUIRES ENHANCED FASTENING. LIMITATION | | NUMBER 7 ON PAGE 45 OF THE NOA REQUIRES | | THAT THESE CALCULATIONS ARE DONE BY AN | | ENGINEER OR ARCHITECT. SUBMIT SIGNED AND | | SEALED CALCULATIONS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | |
|