Plan Review Notes
Plan Review Notes For Permit 06030995
Permit Number 06030995
Review Stop B
Sequence Number 1
Notes
Date Text
2006-03-24 00:00:00DENIED
  
 1) THE PRODUCT APPROVAL SUBMITTED FOR
 THE FLAT ROOF IS FOR STEEL DECKS. THE
 BUILDING PLANS ON FILE INDICATE A
 CONCRETE DECK.
  
 2) SUBMIT RAS 117 CALCULATIONS FOR THE
 FLAT ROOF SYSTEM ENHANCED FASTENING.
  
 3) SPECIFY THE METHOD OF ATTACHMENT THAT
 WILL BE USED TO SECURE THE CLAY TILE.
 CIRCLE THE APPROPRIATE FASTENER TYPE ON
 THE NOA. NOTE: THE ATTACHMENT RESISTANCE
 MUST MEET OR EXCEED THE UPLIFT MOMENT
 REQUIRED FOR THE STRUCTURE.
  
 4) PRODUCTS FOR FLAT ROOF AND CLAY ROOF
 TILES ARE NOT THE SAME AS THE ONES WITH
 THE APPROVED PLANS. A REVISION WILL BE
 REQUIRED.
  
 5) THE MASTER PERMIT LISTS IMPACT
 ROOFING AS THE ROOFING SUBCONTRACTOR. IN
 ORDER TO GET A PERMIT FOR THE NEW
 CONTRACTOR, TWO OPTIONS ARE AVAILABLE. A
 NOTARIZED LETTER FROM THE EXISTING
 ROOFING CONTRACTOR TRANSFERING THE
 EXISTING PERMIT TO THE NEW CONTRACTOR
 WITH A FEE FOR CHANGE OF CONTRACTOR IS
 ONE OPTION. THE OTHER IS TO SUBMIT A
 NOTARIZED LETTER FROM THE BUILDING
 CONTRACTOR STATING THAT THE PREVIOUS
 ROOFING SUBCONTRACTOR HAS BEEN
 TERMINATED AND THE EXISTING ROOFING
 PERMIT WILL BE VOIDED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  