2006-03-24 00:00:00 | DENIED |
| |
| 1) THE PRODUCT APPROVAL SUBMITTED FOR |
| THE FLAT ROOF IS FOR STEEL DECKS. THE |
| BUILDING PLANS ON FILE INDICATE A |
| CONCRETE DECK. |
| |
| 2) SUBMIT RAS 117 CALCULATIONS FOR THE |
| FLAT ROOF SYSTEM ENHANCED FASTENING. |
| |
| 3) SPECIFY THE METHOD OF ATTACHMENT THAT |
| WILL BE USED TO SECURE THE CLAY TILE. |
| CIRCLE THE APPROPRIATE FASTENER TYPE ON |
| THE NOA. NOTE: THE ATTACHMENT RESISTANCE |
| MUST MEET OR EXCEED THE UPLIFT MOMENT |
| REQUIRED FOR THE STRUCTURE. |
| |
| 4) PRODUCTS FOR FLAT ROOF AND CLAY ROOF |
| TILES ARE NOT THE SAME AS THE ONES WITH |
| THE APPROVED PLANS. A REVISION WILL BE |
| REQUIRED. |
| |
| 5) THE MASTER PERMIT LISTS IMPACT |
| ROOFING AS THE ROOFING SUBCONTRACTOR. IN |
| ORDER TO GET A PERMIT FOR THE NEW |
| CONTRACTOR, TWO OPTIONS ARE AVAILABLE. A |
| NOTARIZED LETTER FROM THE EXISTING |
| ROOFING CONTRACTOR TRANSFERING THE |
| EXISTING PERMIT TO THE NEW CONTRACTOR |
| WITH A FEE FOR CHANGE OF CONTRACTOR IS |
| ONE OPTION. THE OTHER IS TO SUBMIT A |
| NOTARIZED LETTER FROM THE BUILDING |
| CONTRACTOR STATING THAT THE PREVIOUS |
| ROOFING SUBCONTRACTOR HAS BEEN |
| TERMINATED AND THE EXISTING ROOFING |
| PERMIT WILL BE VOIDED. |
| |