2006-08-23 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06010452/ 06030925
  
 ADD:422 SUNSET/ 433 AVON RD
 CONT: BURKHARDT CONSTRUCTION
 TEL: (561)659-1400
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC TABLE 601
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
 2A)THE UNITY OF TITLE SUBMITTED IS NOT
 FOR THE LOTS BACK TO BACK, PHASE I AND
 PHASE II BUT FOR THE LOTS THAT ARE ON
 BOTH SIDES OF SUNSET. THIS IS A MATTER
 THAT ZONING, UTILITIES NOR THE LAW
 DEPARTMENT HAS APPROVED. THIS ISSUE HAS
 TO BE RESOLVED BEFORE A PERMIT WILL BE
 ISSUED.
 2B)ALSO SHEET A-1 PHASE-I REMOVE THE
 FENCE FROM ACROSS THE RITE OF WAY BEFORE
 A PERMIT WILL BE ISSUED.
 2C)PROVIDE A UNITY OF TITLE THAT HAS
 BEEN APPROVED FOR LOTS 116 AND 142
 COMBINING THESE LOTS INTO A SINGLE LOT.
  
 3) CONFLICT OR DISCREPANCY IN PLANS AND
 THE ARHITECTS RESPONSE. SHEET A-1
 PHASE-II ITEM# 17 INDICATES THAT THIS IS
 A NEW OVERHEAD FIRE RATED DOOR, WHEREAS
 COMMENT# 8 RESPONSE (06030925) INDICATES
 THIS IS AN EXISTING 3HR FIRE RATED
 DOORWAY. WHICH IS IT, SINCE THIS CROSSES
 PROPERTY LINES NO PERMIT WAS PULLED
 PROVIDE LITERATURE ON THE FIRE RATING
 SINCE WE STILL NEED A 2 HR SEPERATION
 FROM THE PAINT SHOP. TABLE 302.1.1.
  
 4) SHEET A-1 PHASE-II INDICATES A NEW
 HANDICAPPED RAMP AS A RESULT OF A
 MEETING BETWEEN THE OWNER, DESIGN TEAM,
 CONTRACTOR AND BUILDING DEPARTMENT.
 11-4.8.4.(2) LANDINGS. ALL LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARENCE. LOWER LANDING IS NOT
 INDICATED ON PLAN. WILL REQUIRE THE
 ELIMINATION OF ANOTHER PARKING SPOT.
  
 5) THE ARCHITECT HAS SUBMITTED A LETTER
 ON DISPROPORTIONATE COST BUT THIS LETTER
 STILL DOES NOT RELIEVE THE OWNER FROM
 VERTICAL ACCESSIBLIITY.
 11-4.1.6(1)(F) NOTHING IN THIS SECTION
 SHALL BE CONSTRUED TO RELIEVE THE OWNER
 OF ANY BUILDING, STRUCTURE OR FACILITY
 FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND
 BELOW OCCUPIABLE GRADE LEVEL, REGARDLESS
 OF WHETHER THE CODE REQUIRES AN ELEVATOR
 TO BE INSTALLED IN SUCH BUILDING,
 STRUCTURE.
 THE DESIGN TEAM HAS CREATED A RAMP
 TO ENTER THE WAREHOUSE PORTION BUT NO
 VERTICAL ACCESSIBLITY TO THE OFFICES.
  
 6A) A-1, PHASE I INDICATES ROOF TOP AIR
 HANDLERS, THE CURB IS TO BE TIED TO THE
 ROOF DECK BY 3"X3" ANGLES NO MENTION AS
 TO HOW THE ANGLES ARE FASTENED TO THE
 ALUMINIUM FRAME.2004 FBC BUILD 1503.1
  
 6B) THESE SAME 3"X3" ANGLES ARE TO BE
 BOLTED TO THE ROOF WHAT TYPE OF WEATHER
 PROOFING IS TO OCCUR AROUND THE BOLTS?
 2004 FBC BUILD 1503.1
  
 6C) M-1.2 PHASE I PLANS INDICATE THE
 HURRICANE SUPPORT DETAIL WITH A 5/8"
 EYEBOLT THROUGHT THE ROOF DECK BUT NO
 MENTION AS TO HOW TO MAKE THE CONNECTION
  
 WEATHER TIGHT? 2004 FBC BUILD 1503.1
  
 7) ONLY ONE COPY OF LISTED ITEMS BELOW
 REQUIRES (2) SUBMITTALS:
 7A) MSDS SHEETS
 7B) CARBON MONOXIDE MONITORING SYSTEM.
  
 8) WORK TO BE COMPLETED UNDER SEPERATE
 PERMIT:
 A) EXTERIOR MOTORIZED OVERHEAD DOORS
 B) PAINT BOOTH, MIXING ROOM & SUPRESSION
 SYSTEM.
 C) GENERATOR, PAD & LANDSCAPE WALL
 D) FUEL TANKS
 E) FENCING ACROSS SUNSET WITH CITY
 APPROVAL.
 F) KLAUS CAR STORAGE RACKS
  
 BUILDING PROVISOS:
 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSELY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORIC SURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026