2006-08-23 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 06010452/ 06030925 |
| |
| ADD:422 SUNSET/ 433 AVON RD |
| CONT: BURKHARDT CONSTRUCTION |
| TEL: (561)659-1400 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 3RD REVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) THE PROPOSED BUILDING STRUCTURE |
| TRANSGRESSES LEGAL BOUNDARY LINES |
| BETWEEN THE LOTS WHICH COMBINE TO FORM |
| 'THE SITE'.A 'UNITY OF TITLE' SHALL BE |
| RECORDED AT THE COUNTY COURTHOUSE. |
| SUBMIT A COPY OF THE RECORDED 'UNITY OF |
| OF TITLE' DOCUMENT SO THAT FBC TABLE 601 |
| BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| NOT APPLICABLE. |
| 2A)THE UNITY OF TITLE SUBMITTED IS NOT |
| FOR THE LOTS BACK TO BACK, PHASE I AND |
| PHASE II BUT FOR THE LOTS THAT ARE ON |
| BOTH SIDES OF SUNSET. THIS IS A MATTER |
| THAT ZONING, UTILITIES NOR THE LAW |
| DEPARTMENT HAS APPROVED. THIS ISSUE HAS |
| TO BE RESOLVED BEFORE A PERMIT WILL BE |
| ISSUED. |
| 2B)ALSO SHEET A-1 PHASE-I REMOVE THE |
| FENCE FROM ACROSS THE RITE OF WAY BEFORE |
| A PERMIT WILL BE ISSUED. |
| 2C)PROVIDE A UNITY OF TITLE THAT HAS |
| BEEN APPROVED FOR LOTS 116 AND 142 |
| COMBINING THESE LOTS INTO A SINGLE LOT. |
| |
| 3) CONFLICT OR DISCREPANCY IN PLANS AND |
| THE ARHITECTS RESPONSE. SHEET A-1 |
| PHASE-II ITEM# 17 INDICATES THAT THIS IS |
| A NEW OVERHEAD FIRE RATED DOOR, WHEREAS |
| COMMENT# 8 RESPONSE (06030925) INDICATES |
| THIS IS AN EXISTING 3HR FIRE RATED |
| DOORWAY. WHICH IS IT, SINCE THIS CROSSES |
| PROPERTY LINES NO PERMIT WAS PULLED |
| PROVIDE LITERATURE ON THE FIRE RATING |
| SINCE WE STILL NEED A 2 HR SEPERATION |
| FROM THE PAINT SHOP. TABLE 302.1.1. |
| |
| 4) SHEET A-1 PHASE-II INDICATES A NEW |
| HANDICAPPED RAMP AS A RESULT OF A |
| MEETING BETWEEN THE OWNER, DESIGN TEAM, |
| CONTRACTOR AND BUILDING DEPARTMENT. |
| 11-4.8.4.(2) LANDINGS. ALL LANDINGS |
| ON RAMPS SHALL NOT BE LESS THAN 60" |
| CLEAR, & THE BOTTOM OF EACH RAMP SHALL |
| HAVE NOT LESS THAN 72" OF STRAIGHT & |
| LEVEL CLEARENCE. LOWER LANDING IS NOT |
| INDICATED ON PLAN. WILL REQUIRE THE |
| ELIMINATION OF ANOTHER PARKING SPOT. |
| |
| 5) THE ARCHITECT HAS SUBMITTED A LETTER |
| ON DISPROPORTIONATE COST BUT THIS LETTER |
| STILL DOES NOT RELIEVE THE OWNER FROM |
| VERTICAL ACCESSIBLIITY. |
| 11-4.1.6(1)(F) NOTHING IN THIS SECTION |
| SHALL BE CONSTRUED TO RELIEVE THE OWNER |
| OF ANY BUILDING, STRUCTURE OR FACILITY |
| FROM THE DUTY TO PROVIDE VERTICAL |
| ACCESSIBILITY TO ALL LEVELS ABOVE AND |
| BELOW OCCUPIABLE GRADE LEVEL, REGARDLESS |
| OF WHETHER THE CODE REQUIRES AN ELEVATOR |
| TO BE INSTALLED IN SUCH BUILDING, |
| STRUCTURE. |
| THE DESIGN TEAM HAS CREATED A RAMP |
| TO ENTER THE WAREHOUSE PORTION BUT NO |
| VERTICAL ACCESSIBLITY TO THE OFFICES. |
| |
| 6A) A-1, PHASE I INDICATES ROOF TOP AIR |
| HANDLERS, THE CURB IS TO BE TIED TO THE |
| ROOF DECK BY 3"X3" ANGLES NO MENTION AS |
| TO HOW THE ANGLES ARE FASTENED TO THE |
| ALUMINIUM FRAME.2004 FBC BUILD 1503.1 |
| |
| 6B) THESE SAME 3"X3" ANGLES ARE TO BE |
| BOLTED TO THE ROOF WHAT TYPE OF WEATHER |
| PROOFING IS TO OCCUR AROUND THE BOLTS? |
| 2004 FBC BUILD 1503.1 |
| |
| 6C) M-1.2 PHASE I PLANS INDICATE THE |
| HURRICANE SUPPORT DETAIL WITH A 5/8" |
| EYEBOLT THROUGHT THE ROOF DECK BUT NO |
| MENTION AS TO HOW TO MAKE THE CONNECTION |
| |
| WEATHER TIGHT? 2004 FBC BUILD 1503.1 |
| |
| 7) ONLY ONE COPY OF LISTED ITEMS BELOW |
| REQUIRES (2) SUBMITTALS: |
| 7A) MSDS SHEETS |
| 7B) CARBON MONOXIDE MONITORING SYSTEM. |
| |
| 8) WORK TO BE COMPLETED UNDER SEPERATE |
| PERMIT: |
| A) EXTERIOR MOTORIZED OVERHEAD DOORS |
| B) PAINT BOOTH, MIXING ROOM & SUPRESSION |
| SYSTEM. |
| C) GENERATOR, PAD & LANDSCAPE WALL |
| D) FUEL TANKS |
| E) FENCING ACROSS SUNSET WITH CITY |
| APPROVAL. |
| F) KLAUS CAR STORAGE RACKS |
| |
| BUILDING PROVISOS: |
| 109.3.10* IMPACT OF CONSTRUCTION. ALL |
| CONSTRUCTION ACTIVITY REGULATED BY THIS |
| CODE SHALL BE PERMORMED IN A MANNER SO |
| AS NOT TO ADVERSELY IMPACT THE CONDITION |
| OF ADJACENT PROPERTY, UNLESS SUCH |
| ACTIVITY IS PERMITTED TO AFFECT SAID |
| PROPERTY PURSUANT TO A CONSENT BY THE |
| APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| CONDITIONS AGREEABLE TO THE APPLICABLE |
| PROPERTY OWNER.THIS INCLUDES BUT IS NOT |
| LIMITED TO THE CONTROL OF DUST, NOISE, |
| WATER OR DRAINAGE RUN-OFF, DEBRIS, AND |
| THE STORAGE OF CONSTRUCTION MATERIALS. |
| NEW CONSTRUCTION ACTIVITY SHALL NOT |
| ADVERSELY IMPACT HISTORIC SURFACE WATER |
| DRAINAGE FLOWS SERVING ADJACENT |
| PROPERTIES, & MAY REQUIRE SPECIAL |
| DRAINAGE DESIGN COMPLYING WITH |
| ENGINEERING STANDARDS TO PRESERVE THE |
| POSITIVE PATTERNS OF THE AFFECTED SITES. |
| ACCORDINGLY, DEVELOPERS, CONTRACTORS, |
| AND OWNERS OF ALL NEW RESIDENTIAL |
| DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| PATIOS, DRIVEWAYS, DECKS, OR SIMILAR |
| ITEMS, ON EXISTING PROPERTIES RESULTING |
| IN A DECREASE IN EXCESS OF 800SQ FT OF |
| PERMEABLE LAND AREA ON ANY PARCELL SHALL |
| AS A PERMIT CONDITION, PROVIDE A |
| PROFESSIONALLY PREPARED DRAINAGE PLAN |
| CLEARLY INDICATING COMPLIANCE WITH THIS |
| PARAGRAPH. UPON COMPLETION OF THE |
| IMPROVEMENT, A CERTIFICATE FROM A |
| LICENSED ENGINEER SHALL BE SUBMITTED TO |
| THE INSPECTOR IN ORDER TO RECEIVE |
| APPROVAL OF THE FINAL INSPECTION. |
| |
| 109.3.10.1 HURICANE PROTECTION. |
| IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| ALLOW CONSTRUCTION RELATED MATERIALS |
| EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| OTHERWISE UNSECURED AT A CONSTRUCTION |
| SITE FROM 24 HRS. AFTER A HURRICANE |
| WATCH HAS BEEN ISSUED UNTIL THE |
| HURRICANE WATCH OR WARNING HAS BEEN |
| LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| EQUIPMENT AND DEBRIS SHALL BE EITHER |
| REMOVED FROM THE CONSTRUCTION SITE OR |
| SECURED IN SUCH A MANNER AS TO MINIMIZE |
| THE DANGER OF SUCH CONSTRUCTION |
| MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| DAMAGE TO PERSONS OR PROPERTY FROM HIGH |
| WINDS. |
| ANY PERSONS WHO FAILS TO COMPLY TO |
| REMOVE OR SECURE THE CONSTRUCTION |
| MATERIALS EQUIPMENT AND DEBRIS WITHIN |
| 24 HRS AFTER A HURRICANE WATCH HAS BEEN |
| ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| EXCEED $500.00. |
| IN ADDITION TO THE ABOVE, A LICENSED |
| CONTRACTOR WHO VIOLATES THIS SECTION |
| SHALL BE SUBJECT TO DISCIPLINE PURSUANT |
| TO SECTION 113 OF THIS CHAPTER. |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |