Plan Review Notes
Plan Review Notes For Permit 06030925
Permit Number 06030925
Review Stop P
Sequence Number 3
Notes
Date Text
2006-08-24 00:00:00DENIED;
 1.ADA DETAIL FOR PHASE 11 ON PAGE A-2
 ONLY SHOWS A DETAIL OF THE LAVATORY.
 DETAIL OF THE WHOLE BATHROOM IS REQUIRED
 SHOW THE TOILET, SHOWER, AND LAVATORY IN
 DETAIL. REQUIREMENTS FOR COMPLIANCE CAN
 BE FOUND, FBC-2004 CHAPTER 11; TOILET,
 11-4.16.1 THRU 11-4.16.6; LAVATORY
 SECTIONS 11-4.19.1 THRU 11-4.19.6;
 SHOWER SECTIONS 11-4.21.1 THRU
 11-4.21.8.
 2.HOT WATER REQUIRED TO SERVICE SINK.
 (SHOW ON PLAN) SHOW LOCATION OF WATER
 HEATER, OR WATER HEATERS, SIZE AND FUEL
 SOURCE.
 3.SANITARY RISER DIAGRAM;
 A)TRENCH DRAIN AND FLOOR DRAIN SHALL
 NOT BE DOUBLE TRAPPED. SEC 1002.1
 B)WHAT IS THE 4" VERTICAL DRAIN AND
 BACK WATER VALVE FOR? NEED MORE
 INFORMATION)
 C)WHY IS A FLOOR DRAIN NEEDED IN THE
 FUTURE PAINT BOOTH? (SECOND REQUEST)
 4.SAND INTERCEPTER; (SECOND REQUEST)
 PLANS MUST BE VIEWED AND APPROVED BY THE
 UTILITY DEPTMENT FOR SIZE AND LOCATION.
 THE CONTACT PERSON IS;
 LYNN MASSON
 PHONE # 822-2271
 FAX# 822-2279
 E-MAIL [email protected]
 5.PLUMBING FIXTURE REQUIREMENT TABLE FOR
 PHASE 11 IS NOT CORRECT. WORK WILL BE
 DONE IN THIS PART OF THE BUILDING.
 PLEASE CHANGE CLASIFICATION TO BUSINESS,
 OR CHANGE BOTH PHASES TO BUSINESS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695