2006-07-15 00:00:00DENIED;
 1.PROVIDE INFORMATION ON SPRAY BOTH. WHY
 WOULD A FLOOR DRAIN BE REQUIRED?
 2.PLEASE SHOW A DETAIL OF NEW HANDICAP
 BATHROOM. BATHROOM MUST MEET FBC-2004
 CHAPTER 11;
 SHOWER SECTIONS 11-4.21.1 THRU
 11-4.21.8.
 LAVATORY SECTIONS 11-19.1
 THRU11-4.19.6
 SHOW TURNING RADIUS IN BATHROOM ON
 DRAWING.
 3.HANDICAP CODE SECTION 11-4.1.3(11)
 BOTH BATHROOMS MUST BE ACCESSIBLE.
 4.MINIMUM PLUMBING FIXTURES, FBC-2004
 PLUMBING TABLE 403.1(8) REQUIRES A MOP
 SINK AND A DRINKING FOUNTAIN. DRINKING
 FOUNTAIN MUST MEET HANDICAP CODE
 SECTIONS 11-4.15.1 THRU 11-4.15.5, AND
 SECTION 11-4.1.3(11).
 5.PLANS MUST BE REVIEW BY THE UTILITY
 DEPARTMENT FOR SIZE AND LOCATION OF SAND
 AND OIL INTERCEPTOR.
 THE CONTACT PERSON IS;
 LYNN MASSON
 PHONE (561) 822-2271
 FAX(561) 822-2279
 [email protected]
 6.DETAIL OF SAND AND OIL INTERCEPTOR IS
 REQUIRED. HOW IS PIPING TO BE INSTALLED
 (INSIDE THE TANK) TYPE OF MATERIAL TANK
 IS MADE FROM. SHOW COMPLIANCE WITH
 SECTIONS 1003.4 THRU 1003.4.2. ALSO
 1003.9 VENT IS REQUIRED.
 7.EMERGENCY EYE WASH AND SHOWER STATION
 SHOULD BE IN A CENTRAL LOCATION NEAR THE
 PAINT STORAGE AND PREP AREA, ALSO A DOOR
 TO THE SPAY BOOTH SHOULD BE ON THE SIDE
 OF THE EMERGENCY EQUIPMENT.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695