2006-07-15 00:00:00 | DENIED; |
| 1.PROVIDE INFORMATION ON SPRAY BOTH. WHY |
| WOULD A FLOOR DRAIN BE REQUIRED? |
| 2.PLEASE SHOW A DETAIL OF NEW HANDICAP |
| BATHROOM. BATHROOM MUST MEET FBC-2004 |
| CHAPTER 11; |
| SHOWER SECTIONS 11-4.21.1 THRU |
| 11-4.21.8. |
| LAVATORY SECTIONS 11-19.1 |
| THRU11-4.19.6 |
| SHOW TURNING RADIUS IN BATHROOM ON |
| DRAWING. |
| 3.HANDICAP CODE SECTION 11-4.1.3(11) |
| BOTH BATHROOMS MUST BE ACCESSIBLE. |
| 4.MINIMUM PLUMBING FIXTURES, FBC-2004 |
| PLUMBING TABLE 403.1(8) REQUIRES A MOP |
| SINK AND A DRINKING FOUNTAIN. DRINKING |
| FOUNTAIN MUST MEET HANDICAP CODE |
| SECTIONS 11-4.15.1 THRU 11-4.15.5, AND |
| SECTION 11-4.1.3(11). |
| 5.PLANS MUST BE REVIEW BY THE UTILITY |
| DEPARTMENT FOR SIZE AND LOCATION OF SAND |
| AND OIL INTERCEPTOR. |
| THE CONTACT PERSON IS; |
| LYNN MASSON |
| PHONE (561) 822-2271 |
| FAX(561) 822-2279 |
| [email protected] |
| 6.DETAIL OF SAND AND OIL INTERCEPTOR IS |
| REQUIRED. HOW IS PIPING TO BE INSTALLED |
| (INSIDE THE TANK) TYPE OF MATERIAL TANK |
| IS MADE FROM. SHOW COMPLIANCE WITH |
| SECTIONS 1003.4 THRU 1003.4.2. ALSO |
| 1003.9 VENT IS REQUIRED. |
| 7.EMERGENCY EYE WASH AND SHOWER STATION |
| SHOULD BE IN A CENTRAL LOCATION NEAR THE |
| PAINT STORAGE AND PREP AREA, ALSO A DOOR |
| TO THE SPAY BOOTH SHOULD BE ON THE SIDE |
| OF THE EMERGENCY EQUIPMENT. |
| PLUMBING PLAN REVIEW BY; |
| JOHN LEECH |
| 805-6695 |