2006-07-17 00:00:00 | DENIED:433 AVON ROAD/BUILDING 1 |
| |
| PLEASE NOTE, MEETING WAS HELD WITH |
| BURKHARDT CONSTRUCTION SEVERAL MONTHS |
| AGO WITH REGARDS TO THE VEHICLE STORAGE |
| AT 422 SUNSET RD. |
| |
| 1.PLEASE CLARIFY WHICH BUILDING WILL |
| BE USED FOR STORAGE AND WHICH BUILDING |
| WILL HAVE THE SPRAY PAINT BOOTH. |
| ACCORDING TO MY NOTES, THE REVIEW UNDER |
| PERMIT 06010452 IS FOR THE PRIVATE CAR |
| STORAGE - BUILDING 1 (REFERENCE PERMIT |
| 06030925).THE PLANS SUBMITTED INDICATE |
| BUILDING 1 AS HAVING A SPRAY PAINT |
| BOOTH. |
| |
| 2.WHERE IN RELATION TO THIS BUILDING 1 |
| IS THE OTHER BUILDING LOCATED? |
| |
| 3.PLEASE PROVIDE INFORMATION ON THE |
| "NEW CAR LIFTS" INDICATED ON PLAN SHEET |
| A-1.PLEASE PROVIDE MANUFACTURER'S |
| SUBMITTAL DATA.PLEASE INDICATE WHAT |
| THE LIFTS ARE NEEDED FOR IF NO |
| MECHANICAL WORK IS TO BE DONE ON THE |
| VEHICLE. |
| |
| 4.MANUFACTURER SUBMITTAL DATA WAS |
| SUBMITTED FOR THE SPRAY BOOTH & PAINT |
| MIXING ROOM.PLEASE INDICATE WHICH |
| MODEL OF THE SPRAY BOOTH WILL BE |
| INSTALLED.PLEASE NOTE, ADDTIONAL |
| PERMIT REQUIRED FOR SPRAY BOOTH & MIXING |
| ROOM. |
| |
| 4.SPRAY PAINT BOOTH TO HAVE A MINIMUM |
| CLEARANCE OF 3 FT ROUND SPRAY BOOTH AND |
| A FIRE RESISTANCE RATING OF 1 HOUR IN |
| ACCORDANCE WITH NFPA 33 SECTION 5.3 & |
| 5.3.2. |
| |
| 5.PLEASE INDICATE TERMINATION OF |
| EXHAUST FROM THE SPRAY BOOTH.INDICATE |
| DISTANCES FROM PROPERTY LINES AND |
| ADJOINED/CONTINGUOUS BUILDINGS. SHOW |
| COMPLIANCE WITH 2004 FMC 502.7.3.6. |
| |
| 6.PLEASE SEE COMMENT #2BY JIM WITMER |
| DATED 7-10-06. |
| |