2006-07-12 00:00:001. ALL VEHICLES ON DISPLAY SHALL HAVE
 THE BATTERIES DISCONNECTED AND CONTAIN
 VERY LITTLE FUEL. THIS ITEM WAS VERIFIED
 WITH OGS&P ON 7/12/06 BY PHONE.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE PROPOSED SPRAY BOOTH AND MIXING
 ROOM. BOTH WILL BE REQUIRED TO BE
 PROTECTED WITH AN AUTOMATIC FIRE
 SUPPRESSION SYSTEM UNDER SEPARATE
 PERMIT. THE SPRAY BOOTH SHALL COMPLY
 WITH NFPA 33.
  
 3. COULD NOT LOCATE ANY CUT SHEETS ON
 CARBON MONOXIDE DETECTORS THAT ARE
 PLANNED FOR USE IN THE LITERATURE.
 PLEASE PROVIDE PRODUCT LITERATURE AND
 HOW WILL THESE DEVICES BE TESTED.
 CALIBRATION GAS AND TEST EQUIPMENT WILL
 MOST LIKELY BE NEEDED IF THE SET POINTS
 ON THESE DETECTORS DO NOT COME FACTORY
 SET. PLEASE PROVIDE MORE DETAILS AS
 REQUIRED.
  
 4. ALL WORK SUBJECT TO FIELD INSPECTION
 AND APPROVAL. PLEASE HAVE THE PROJECT
 ARCHITECT CONTACT THIS OFFICE AT
 804-4709. THANK YOU.
  
 APPROVED PROVISO
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER