Plan Review Notes For Permit 06030925 |
Permit Number |
06030925 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-07-12 00:00:00 | 1. ALL VEHICLES ON DISPLAY SHALL HAVE | | THE BATTERIES DISCONNECTED AND CONTAIN | | VERY LITTLE FUEL. THIS ITEM WAS VERIFIED | | WITH OGS&P ON 7/12/06 BY PHONE. | | | | 2. SEPARATE PLANS AND PERMITS REQUIRED | | FOR THE PROPOSED SPRAY BOOTH AND MIXING | | ROOM. BOTH WILL BE REQUIRED TO BE | | PROTECTED WITH AN AUTOMATIC FIRE | | SUPPRESSION SYSTEM UNDER SEPARATE | | PERMIT. THE SPRAY BOOTH SHALL COMPLY | | WITH NFPA 33. | | | | 3. COULD NOT LOCATE ANY CUT SHEETS ON | | CARBON MONOXIDE DETECTORS THAT ARE | | PLANNED FOR USE IN THE LITERATURE. | | PLEASE PROVIDE PRODUCT LITERATURE AND | | HOW WILL THESE DEVICES BE TESTED. | | CALIBRATION GAS AND TEST EQUIPMENT WILL | | MOST LIKELY BE NEEDED IF THE SET POINTS | | ON THESE DETECTORS DO NOT COME FACTORY | | SET. PLEASE PROVIDE MORE DETAILS AS | | REQUIRED. | | | | 4. ALL WORK SUBJECT TO FIELD INSPECTION | | AND APPROVAL. PLEASE HAVE THE PROJECT | | ARCHITECT CONTACT THIS OFFICE AT | | 804-4709. THANK YOU. | | | | APPROVED PROVISO | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | OFFICER | | 804-4709 |
|