Plan Review Notes
Plan Review Notes For Permit 06030925
Permit Number 06030925
Review Stop E
Sequence Number 2
Notes
Date Text
2006-07-02 00:00:00IN ELEC FOR REVIEW
 ******** UNSAT 2ND REVIEW ********
  
  
 1) NOTE: PLEASE SEE ELECTRICAL PLANS
 WHICH DID NOT INDICATE VEHICLE LIFTS AND
 SPRAY BOOTH ON PREVIOUS PLANS, NOW
 INDICATE THIS AS SOME SORT OF SERVICE
 REPAIR/BODY SHOP.
 PLEASE SEE NEC 511 AND 516. ALL AREAS AN
 CLASS LOCATION SHALL BE INDICATED AND
 LAYED OUT PER NEC 500, 500.5, 501, CLASS
 1 DIV 1, CLASS 1 DIV 2?
 NFPA-88B, 1997
 PLEASE SEE THIS SHOWN WITH A "WAREHOUSE"
 OCCUPANCY WHICH DOES NOT SEEM TO
 CORRELATE WITH NEW REVISED PLANS AND
 PROPOSED WORK.
  
 2) NOTE: PLEASE SEE PLANS NOW INDICATE
 AN OPEING TO ADJACENT SPACE WHICH IS
 ANOTHER TENANT, ADDRESS AND OCCUPANCY
 FOR "VEHICLE STORAGE".
 THIS ADDITONAL METERED SERVICE MAY NOT
 BE GRANTED AT THIS TIME.
 "SEPARATION" IS NOT ACHEIVED BY THE
 OVERHEAD DOOR, AS THIS CAN BE OPENED AT
 ANY TIME AND LEFT IN THE OPEN POSITION.
 PLEASE SEE TWO DIFFERENT PROJECTS ARE
 COMING IN FOR PERMIT, WHICH SEEM TO BE
 INFACT THE SAME BUSINES, SPACE ETC.
 ** PLEASE KNOW, THESE ARE BEING STATED
 AS TWO SEPARATE "BUILDINGS"?? PLEASE SEE
 DEFINITIONS OF "BUILDING" AND SEPARATION
 REQUIRED BYE A "FIREWALL". PLEASE SEE
 "FIREWALL" AND CONSTRUCT ACCORDINGLY.
 PLEASE KNOW, AT THAT TIME THE SECOND
 SERVICE AND METER WILL BE GRANTED.
 230.2
  
  
 3) NOTE: PLEASE SEE THAT PLANS REFLECT
 ALL CURRENT CODES IN EFFECT.
 NFPA-70 2002, NFPA-101 2003, NFPA-72
 2002 AND FBC 2004. PLEASE SEE PLANS
 REFERENCE THE 2001 FBC.
  
 4) NOTE:PLEASE SEE FBC CHAPTER 13
 WHICH APPLIES TO THIS SPACE.
 PLEASE PROVIDE LIGHTING DENSITES FOR
 AREAS.
 PLEASE PROVIDE OVER RIDES AS REQUIRED
 AND INDICATE THE MAX AMOUNT OF TIME FOR
 DEVICES CHOSEN. (TIMERS 4HRS MAX) , OCC
 SENSORS 30MINS MAX).
 PLEASE SEE ENERGY CALCULATIONS SHALL BE
 SIGNED, DATED AND SEALED BY ALL DESIGN
 PROFESSIONALS RESPONSIBLE.
 PLEASE SEE THESE ONLY CONTAIN A
 SIGNATURE AT THIS TIME.
 PLEASE SEE 13-415.1.ABC.1.1,.1.2,.1.3
 PLEASE SEE 13-415.1.AB.1,
 13-415.2.ABC.1, AND TABLES 415.2.C1,
 415.2.B.1
  
 5) NOTE: PLEASE KNOW, "IF" ADDITIONAL
 SERVICE IS GRANTED , PLEASE BOND BOTH
 SERVICES AT THE GROUNDING ELECTRODE
 SYSTEM.250.94,250.90 ETC
  
 6) NOTE: ** IMPORTANT" AS REQUESTED BY
 THE BUIDLING REVIEWER ON PREVIOUS NOTES:
 ONCE ALL REVIEWS ARE COMPLETE, BEFORE
 RESUBMITTING PLANS, PLEASE COMPLETELY
 REMOVE ALL OLD/VOIDED SHEETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING. ONE COPY
 OF THE OLD/VOIDED REMOVED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP TO ALLEAVIATE ANY DELAYS
 INTHE PROCESS.
  
 ** PLEASE KNOW, ONE SET OF EACH OF THE
 PREVIOUS SUBMITTED ELECTRICAL PLANS
 ALONG WITH THE NEW REVISED ELECTRICAL
 PLANS ARE BEING RETAINED BY THIS OFFICE
 AS EACH SET CONTAINS COMPLETELY
 DIFFERENT INFORMATION FOR USE/OCCUPANCY
 ETC.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELETRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, OR COMMENTS
 PLEASE CALL.
 A CALLED WAS PLACED TO THE ELECTRICAL
 ENGINEER'S OFFICE AND A MESSAGE WAS LEFT
 AS OF THIS REVIEW TO GO OVER PLANS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]