Plan Review Notes
Plan Review Notes For Permit 06030925
Permit Number 06030925
Review Stop B
Sequence Number 2
Notes
Date Text
2006-07-10 00:00:00BUILDING PLAN REVIEW
 PERMIT:06030925
 ADD: 433 AVON RD
 CONT: BURCHANDT CONSTRUCTION
 TEL: (561)718-2602
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICA TION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) COMMENET # 5A FROM THE PREIOUS
 REVIEW, DEALS WITH THE OPENINGS ON THE
 WEST SIDE OF THE BUILDING. IN THE
 MEETING WE HAD IT APPEARS THERE IS A
 MISS-UNDERSTANDING OF THE LEVEL II WORK
 ON THAT WALL. IF THE EXISTING WINDOWS
 THAT ARE A CODE VIOLATION TABLE 602, ARE
 NOT TOUCHED THEY MAY STAY, NO NEW
 OPENINGS CAN BE MADE WHEN REPLACING
 WINDOWS THE OLD ONES ARE REMOVED HENCE
 THEY CAN BE BLOCKED INREDUCING THE
 FIRE LOADAT THE PROPERTY LINE WALL.
  
 5B) COMPLIES, WITH A SEPERATE PERMIT TO
 BE APPLIED FOR BY SPECIALTY CONTRACTOR
 FOR THE PAINT BOOTH AND MIXING ROOM.
 903.4(5) COMPLIES WITH THROUGH ALTERNATE
 METHODS AND MATERIALS (FIRE SUPRESSION
 SYSTEM-DRY CHEMICAL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026