2006-04-25 00:00:00*** DENIED ***
 1) PLEASE PROVIDE MINIMUM VENTILATION
 0.05 CFM PER SQUARE FOOT, PER. 2004
 FBC/M 404.2 .
  
 2) PLEASE CORRECT LOW LEVEL ALARM TO 25
 PARTS PER MILLION, PER 2004 FBC/M 404.1
 ENCLOSED PARKING GARAGES.
  
 3) PLEASE SHOW ON MECHANICAL PLANS A/C
 ROOF EQUIP. MOUNTING DETAILS THAT THIS
 COMPLIES WITH 2004 FBC/M 301.13 AND WITH
 STANDS 140 MPH WINDS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.