Plan Review Notes For Permit 06030925 |
Permit Number |
06030925 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-04-25 00:00:00 | *** DENIED *** | | 1) PLEASE PROVIDE MINIMUM VENTILATION | | 0.05 CFM PER SQUARE FOOT, PER. 2004 | | FBC/M 404.2 . | | | | 2) PLEASE CORRECT LOW LEVEL ALARM TO 25 | | PARTS PER MILLION, PER 2004 FBC/M 404.1 | | ENCLOSED PARKING GARAGES. | | | | 3) PLEASE SHOW ON MECHANICAL PLANS A/C | | ROOF EQUIP. MOUNTING DETAILS THAT THIS | | COMPLIES WITH 2004 FBC/M 301.13 AND WITH | | STANDS 140 MPH WINDS. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|