Plan Review Notes
Plan Review Notes For Permit 06030925
Permit Number 06030925
Review Stop E
Sequence Number 1
Notes
Date Text
2006-04-14 00:00:00***** UNSAT *****
  
 1) NOTE: PLEASE PROVIDE NOTE FOR TYPE OF
 TIME CLOCK BEING INSTALLED FOR LIGHTING
 CONTROL SYSTEM. IS THIS AN ASTRONOMICAL
 TYPE OF CLOCK?
 FBC CHAPTER 13. 13-415.1.ABC.1.1
 PLEASE PROVIDE SCHEDULE FOR RELAY PANEL
 /DETAIL FOR THIS.
  
 2) NOTE: PLEASE SUBMIT MANUFACTURES
 SPECS/CUT SHEETS FOR ATS WHICH IS BEING
 INSTALLED FOR FUTURE GEN.
 215.5
  
 3) NOTE: PLEASE CLARIFY THE MEANS OF
 DISCONNECT WHICH WILL BE REQUIRED FOR
 GEN FEEDERS. IS THE MDP PANEL GROUPED
 WITH THE MAIN AND ATS? IF THE MDP IS
 GROUPED AND CONTAINS A MCB FOR
 DISCONNECTING POWER THEN A SEPARATE
 DISCONNECT WOULD NOT BE REQUIRED.
 PLEASE INDICATE THE LOCATION ON PLANS OF
 THE MDP AND ATS.
 215.5,225.31-225.39
  
 4) NOTE: PLEASE VERIFY NEW SERVICE AS
 SHOWN. PLANS INDICATE AN EXISTING
 SERVICE AND MAIN. IT IS NOT KNOWN AT
 THIS TIME IF AN ADDITIONAL SERVICE IS
 PERMITTED PER 230.2
  
 5) NOTE: PLEASE SEE 700.12E FOR
 CICUITING OF EM/EXT LTS.
 *EXCPT*
  
 6) NOTE: PLEASE CLARIFY IF THE
 CONTINUOUS / LIGHTING LOADS ARE SHOWN AT
 125%.215.3,230.42
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALLL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]