2006-05-08 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT:06030925 |
| ADD: 433 AVON RD |
| CONT: BURCHANDT CONSTRUCTION |
| TEL: (561)718-2602 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE & REPLACE |
| ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUM- BER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET |
| OR SPECIFICA TION PAGE WHERE THE CHANGES |
| CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 2) 110.2* W. P. B. ADMINISTRATIVE CODE, |
| INFORMATION THAT IS REQUIRED FOR RECORD |
| KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| A) THE EDITION OFTHE CODE UNDER WHICH |
| THE PERMIT WAS ISSUED. |
| B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| WITH THE PROVISIONS OF CHAPTER 3. |
| C) THE TYPE OF CONSTRUCTION AS DEFINED |
| IN CHAPTER 6, TABLE 601. |
| D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| IS REQUIRED. |
| F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| OF THE BUILDING PERMIT. |
| |
| 3) 109.3.10.1 HURICANE PROTECTION. |
| IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| ALLOW CONSTRUCTION RELATED MATERIALS |
| EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR |
| OTHERWISE UNSECURED AT A CONSTRUCTION |
| SITE FROM 24 HRS. AFTER A HURRICANE |
| WATCH HAS BEEN ISSUED UNTIL THE |
| HURRICANE WATCH OR WARNING HAS BEEN |
| LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| EQUIPMENT AND DEBRIS SHALL BE EITHER |
| REMOVED FROM THE CONSTRUCTION SITE OR |
| SECURED IN SUCH A MANNER AS TO MINIMIZE |
| THE DANGER OF SUCH CONSTRUCTION |
| MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| DAMAGE TO PERSONS OR PROPERTY FROM |
| HIGHWINDS. |
| ANY PERSONS WHO FAILS TO COMPLY TO |
| REMOVE OR SECURE THE CONSTRUCTION |
| MATERIALS EQUIPMENT AND DEBRIS WITHIN |
| 24 HRS AFTER A HURRICANE WATCH HAS BEEN |
| ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| EXCEED $500.00. |
| IN ADDITION TO THE ABOVE, A LICENSED |
| CONTRACTOR WHO VIOLATES THIS SECTION |
| SHALL BE SUBJECT TO DISCIPLINE PURSUANT |
| TO SECTION 113 OF THIS CHAPTER. |
| |
| 4) WPB ADMIN105.9* |
| FL S S 469. THIS AGENCY IS THE LOCAL |
| ASBESTOS AUTHORITY, AND SHOULD RECEIVE |
| ALL NOTIFICATIONS FOR BUILDING |
| DEMOLITION OR RENOVATION PROJECTS. |
| CONTACT THEM FOR GENERAL INFORMATION ON |
| ASBESTOS ISSUES INCLUDING REGULATIONS, |
| CONTRACTORS OR CONSULTANTS.FL SS 469.003 |
| PALM BEACH COUNTY PUBLIC HEALTH UNIT |
| (DIVISION OF ENVIROMENTAL SCIENCE & |
| ENGINEERING AIR POLLUTION CONTROL |
| SECTION) |
| 901 EVERNIA STREET |
| WEST PALM BEACH, FL 33401 |
| (561)366-3070 |
| |
| 5) SHEET A-1: |
| 5A) WEST ELEVATION, PROVIDE INFORMATION |
| HOW CLOSE THIS BUILDING IS TO THE |
| PROPERTY LINE? TABLE TABLE 602. |
| |
| 5B) PLANS INDICATE A PROPOSED PAINT |
| SPRAY BOOTH, PROVIDE DETAIL SHEETS. |
| |
| 5C) PLANS INDICATE NEW WALLS ABOVE THE |
| RESTROOMS, A EQUIPMENT PLATFORM. DETAIL# |
| 8 DOESN'T INDICATE IF THE METAL STUDS |
| ARE DRYWALL OR STRUCTURAL RATED? |
| ARE THE STAIRS GOING TO THE PLATFORM NEW |
| ALSO? NO DETAILS? |
| 505.5 INDUSTRIAL EQUIPMENT PLATFORMS. |
| INDUSTRIAL EQUIPMENT PLATFORMS IN |
| BUILDINGS SHALL NOT BE CONSIDERED AS A |
| PORTION OF THE FLOOR BELOW. SUCH |
| EQUIPMENT PLATFORMS SHALL NOT CONTRIBUTE |
| TO EITHER THE BUILDING AREA OR THE |
| NUMBER OF STORIES AS REGULATED BY |
| SECTION 503.1 . THE AREA OF THE |
| INDUSTRIAL EQUIPMENT PLATFORM SHALL NOT |
| BE INCLUDED IN DETERMINING THE FIRE |
| AREA. INDUSTRIAL EQUIPMENT PLATFORMS |
| SHALL NOT BE A PART OF ANY MEZZANINE, |
| AND SUCH PLATFORMS AND THE WALKWAYS, |
| STAIRS AND LADDERS PROVIDING ACCESS TO |
| AN EQUIPMENT PLATFORM SHALL NOT SERVE AS |
| A PART OF THE MEANS OF EGRESS FROM THE |
| BUILDING. |
| |
| 505.5.1 AREA LIMITATIONS. |
| THE AGGREGATE AREA OF ALL INDUSTRIAL |
| EQUIPMENT PLATFORMS WITHIN A ROOM SHALL |
| NOT EXCEED TWO-THIRDS OF THE AREA OF THE |
| ROOM IN WHICH THEY OCCUR. WHERE AN |
| EQUIPMENT PLATFORM IS LOCATED IN THE |
| SAME ROOM AS A MEZZANINE, THE AREA OF |
| THE MEZZANINE SHALL BE DETERMINED BY |
| SECTION 505.2 , AND THE COMBINED |
| AGGREGATE AREA OF THE EQUIPMENT |
| PLATFORMS AND MEZZANINES SHALL NOT |
| EXCEED TWO-THIRDS OF THE ROOM IN WHICH |
| THEY OCCUR. |
| |
| 6) THE SOUTHEAST CORNER OF THE BUILDING |
| A PLATFORM AND STAIRWAY ARE CONSTRUCTED, |
| PROVIDE MORE DETAILS? |
| |
| 7A)1609.1.4 PROTECTION OF OPENINGS. |
| IN WIND-BORNE DEBRIS REGIONS, EXTERIOR |
| GLAZING THAT RECEIVES POSITIVE PRESSURE |
| IN THE LOWER 60 FEET (18.3 M) IN |
| BUILDINGS SHALL BE ASSUMED TO BE |
| OPENINGS AND THE BALANCE OF GLAZED |
| OPENINGS IN THE REST OF THE BUILDING |
| SHALL BE ASSUMED TO BE ZERO UNLESS SUCH |
| GLAZING THAT RECEIVES POSITIVE PRESSURE |
| IS IMPACT RESISTANT OR PROTECTED WITH AN |
| IMPACT RESISTANT COVERING MEETING THE |
| REQUIREMENTS OF SSTD 12, ASTM E 1886 AND |
| ASTM E 1996, OR MIAMI-DADE TAS 201, 202 |
| AND 203 REFERENCED THEREIN AS FOLLOWS: |
| 1.GLAZED OPENINGS LOCATED WITHIN 30 |
| FEET (9.1 M) OF GRADE SHALL MEET THE |
| REQUIREMENTS OF THE LARGE MISSILE TEST. |
| 2.GLAZED OPENINGS LOCATED MORE THAN |
| 30 FEET (9.1 M) ABOVE GRADE SHALL MEET |
| THE PROVISIONS OF THE SMALL MISSILE |
| TEST. |
| |
| 7B) PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 7C) WPB ADMIN CODE 106.3* PRODUCT |
| APPROVALS. THOSE PRODUCT WHICH ARE |
| REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 7D) FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| 1) WINDOWS |
| 2) MOTORIZED OVERHEAD DOORS |
| 3) STOREFRONT WINDOWS |
| 4) STOREFRONT DOORS |
| 5) MULLIONS |
| |
| 8) PROVIDE INFORMATION ON COMPLIANCE |
| WITH TABLE 302.1.1PAINT SHOP 2HR |
| SEPERATION OR 1HR AND PROVIDE AUTOMATIC |
| FIRE -EXTINGUISHING SYSTEM. |
| |
| 9) PROVIDE THE AMOUNT OF PAINT AND |
| SOLVENTS TO BE STORED ON SITE AND |
| FLAMMIBLITY, THIS WILL DICTATE OCCUPANCY |
| SEE CONTROL AREAS TABLE 307.7(1) |
| |
| 10) PROVIDE MSDS SHEETS FOR THE ABOVE |
| MATERIALS. |
| BUILDING PLAN REVIEW |