2006-03-27 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2004 |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| TO THE FBC2004 |
| |
| SHUTTER PERMIT APPLICATION, ONLY CHECKED |
| ITEMS APPLY |
| |
| _XX_1.A NOTICE OF COMMENCEMENT MUST |
| BE FILED WITH THE CLERK OF COURTS BEFORE |
| A PERMIT CAN BE ISSUED, FS713.13. |
| |
| ____2.PROVIDE BUILDING HEIGHT. |
| DESIGN PRESSURES FOR BUILDINGS OVER |
| 60FEET ARE REQUIRED TO BE DESIGNED USING |
| ASCE7, FBC1609.1.1. DOCUMENTS PREPARED |
| BY AN ENGINEER AND SUBMITTED FOR PUBLIC |
| RECORD ARE TO BE SIGNED SEALED ORIGINALS |
| FAC61G15-23.002. |
| |
| ____3.PROVIDE A COPY OF THE CONDO |
| ASSOCIATION APPROVAL. |
| |
| ____4.COMPLETE THE ATTACHED |
| INSTALLATION SCHEDULE OR PROVIDE |
| REQUIRED INFORMATION IN A SIMILAR |
| FORMAT.YOU MAY SHOW ANCHOR SPACING BY |
| CIRCLING IT ON THE APPROPRIATE CHARTS ON |
| THE PRODUCT APPROVAL. |
| |
| ____5.FLORIDA STATE OR LOCAL PRODUCT |
| APPROVAL REQUIRED, FAC9B72, |
| WWW.FLORIDABUILDING.ORG. |
| |
| _XX_6.ON THE PRODUCT APPROVAL, MARK |
| WHICH DETAILS APPLY TO THIS JOB.PLEASE |
| USE INK RATHER THAN A HIGHLIGHTER (NOTE |
| THAT A YELLOW HIGHLIGHTER DOES NOT |
| DIGITIZE, AND OTHER COLORS MAKES THE |
| TEXT ILLEGIBLE WHEN DIGITIZED). |
| |
| ____7.SHOW THE EMERGENCY MEANS OF |
| ESCAPE, FBC R310. |
| |
| ____8.PROVIDE A FLOOR PLAN SHOWING |
| WHERE THE SHUTTERS WILL BE INSTALLED |
| WHICH CORRELATES WITH THE INSTALLATION |
| SCHEDULE, ITEM 4 ABOVE. |
| |
| _XX_ 9.REVISE THE DESIGN PRESSURES. |
| YOU ARE STATING THAT THE DESIGN PRESSURE |
| IS +24.6, BUT THERE IS NOTHING THAT LOW |
| ON THE CHART FBC TABLE 1609.6B.IT IS |
| ALSO NOT CLEAR HOW YOU HAVE ARRIVED AT |
| THE NEGATIVE PRESSURES.IT APPEARS THAT |
| THE ANCHORING IS COMPLIANT; HOWEVER, |
| INCORRECT PAPERWORK CANNOT BE APPROVED. |
| PLEASE CONTACT ME IF YOU NEED FURTHER |
| ASSISTANCE.A COPY OF THE TABLE IS |
| ENCLOSED FOR YOUR CONVENIENCE. |
| |