Notes |
Date |
Text |
2006-04-13 00:00:00 | ******DENIED****** | | | | 1) SPEC SHEETS INDICATE DUCT SMOKE | | DETECTORS, HOWEVER NONE ARE SHOWN ON THE | | PLANS OR RISER. | | | | 2) IT APPEARS THAT ONLY (1) SET OF SPEC | | SHEETS WERE SUBMITTED. PLEASE SUBMIT | | SHEETS WITH EACH SET OF DRAWINGS. IF (2) | | SETS WERE SUBMITTED, PLEASE SEPARATE. | | | | 3) FIRE ALARM SHALL BE UL CERTIFIED FOR | | CENTRAL STATION SERVICE. | | | | 4) DUCT SMOKE DETECTORS SHALL INITIATE A | | GENERAL FIRE ALARM IN ACCORDANCE WITH | | LOCAL REQUIREMENTS. | | | | 5) FIRE ALARM TO BE CLASS A OR FULLY | | ADDRESSABLE. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|