2006-04-13 00:00:00******DENIED******
  
 1) SPEC SHEETS INDICATE DUCT SMOKE
 DETECTORS, HOWEVER NONE ARE SHOWN ON THE
 PLANS OR RISER.
  
 2) IT APPEARS THAT ONLY (1) SET OF SPEC
 SHEETS WERE SUBMITTED. PLEASE SUBMIT
 SHEETS WITH EACH SET OF DRAWINGS. IF (2)
 SETS WERE SUBMITTED, PLEASE SEPARATE.
  
 3) FIRE ALARM SHALL BE UL CERTIFIED FOR
 CENTRAL STATION SERVICE.
  
 4) DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 5) FIRE ALARM TO BE CLASS A OR FULLY
 ADDRESSABLE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722