Plan Review Notes
Plan Review Notes For Permit 06030769
Permit Number 06030769
Review Stop E
Sequence Number 1
Notes
Date Text
2006-03-20 00:00:00 
 PLEASE SUBMIT THE SIZE OF THE SERVICE
 CONDUCTORS PER 310.16, THE GROUNDING
 ELECTRODE CONDUCTOR PER 250.66 AND
 INDICATE THE MAIN DISCONNECT LOCATION
 AND AIC RATING.
  
 PLEASE CORRECT THE DESCRIPTION ON THE
 APPLICATION TO INDICATE IF THE METER AND
 PANEL ARE BEING REPLACED, OR JUST THE
 METER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW