Plan Review Notes
Plan Review Notes For Permit 06030622
Permit Number 06030622
Review Stop M
Sequence Number 2
Notes
Date Text
2006-04-07 00:00:00*** DENIED ***
 1) PLEASE CHECK AND CORRECT THE CEILING
 HEIGHT FOR THE SECOND FLOOR ON THE
 MANUAL J CAL'S. (THE CEILING HEIGHT IS
 NOT 20 FT., IT IS 9' 6").
  
 2) PLEASE MAKE CORRECTIONT TO MECHANICAL
 PLANS AS A RESULT OF THE NEW MANUEL J .
  
 3) PLEASE SHOW A/C EQUIPMENT LIST WITH
 ALL PERTINENT INFORMATION, ON MECHANICAL
 PLANS .
  
 4) PLEASE SHOW JOB ADDRESS ON ALL PAGES
 OF THE MECHANICAL PLANS, LOT A IS NOT AN
 ADDRESS.
  
 5) PLEASE SUBMIT TWO COPYS OF ALL
 DOCUMENTS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.