Date Text
2006-03-20 00:00:00*** DENIED ***
 1) PLANS MAY NOT BE DONE IN PENCIL.
  
 2) PLEASE SUBMIT TWO COPYS OF PLANS.
 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 3) PLEASE SHOW ON MECHANICAL PLANS AN
 EQUIPMENT LISTING WITH MANUFACTURE NAME,
 MODEL NUMBER, TONS, SEER, HEATER KW,
 TOTAL COOLING BTU'S; SENSIBLE COOLING
 BTU'S; AND COPPER LINE SIZES.
  
 4) AS REQUESTED IN LAST REVIEW, PLEASE
 SIGN BOLTH COPYS OF ENERGY CAL'S.
  
 5) PLEASE SHOW SIZE OF SUPPLY AIR DUCT
 (FLEX) FROM AHU TO TO THE MIXING BOX.
  
 6) PLEASE SUPPLY RETURN AIR TO THE
 BEDROOMS, SEE NOTE #7.
  
 7)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 8) PLEASE PROVIDE LIABILITY INSURANCE
 INFORMATION FOR EWING & EWING AIR COND.
 NOT EWING HEATING & AIR INC..
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.