2006-07-16 00:00:00IN ELEC FOR REVIEW, FROM ZONING ON 7/11
 **** UNSAT ****
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE SOME NEW NOTES.
  
 ** PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW AS NOTED,
 WITH NEW NOTES ADDED TO THE BOTTOM OF
 THE FIRST REVIEW NOTES.
  
  
  
 1) NOTE: OK.
  
 2) NOTE: OK.
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE: OK/NO. ADDRESSED COMMENT,
 HOWEVER DUE TO CHANGES MADE BY COMMENT,
 PLEASE SEE THE MISPRINT WAS REVISE,
 HOWEVER PLEASE KNOW, THE CONDUIT
 EXTENDING FROM GRND TO METER SHALL BE
 SCHEDULE 80 AS THIS IS AREA IS
 CONSIDERED SUBMIT TO PHYSICAL DAMAGE.
 352.10F
  
 ** PREVIOUS REVIEW NOTE**PLEASE SEE
 UNDERGROUND CONDUITS
 WHICH MENTIONS THE USE OF SCHEDULE "90"
 PVC?? PLEASE VERIFY AS THIS IS NOT A
 COMMON ITEM, NOR IS IT LISTED IN THE
 NEC.
 215.5
  
 6) NOTE: OK.
  
 7) NOTE: OK.
  
 8) NOTE: NO, PLEASE SEE THIS STILL DOES
 NOT SEEM TO BE COMPLETE AT THIS TIME FOR
 INTENDED LOADS, DISCONNECTING MEANS ECT.
 PLEASE ALSO SEE THAT MANUFACTURES
 SPECS/CUT SHEETS WERE NOT SUBMITTED.
 PLEASE KNOW, IT IS NOTED THAT THE
 RESPONSE MENTIONS THIS WOULD BE DONE AT
 A LATER DATE , HOWEVER THIS IS REQUIRED
 AT THIS TIME IF SYSTEM IS GOING TO BE
 UNDER MAIN HOUSE PERMIT. PLEASE SEE
 PLANS ARE NOT DETAILED ENOUGH FOR
 TRANSFER OF POWER AND WHERE THAT IS
 TAKING PLACE, DISCONNECTING MEANS ETC.
 ** PLEASE KNOW, THE PV SYSTEM MAY
 EXCLUDED AND SUBMITTED UNDER A SEPARATE
 PERMIT AT A LATER DATE. NO ELECTRICAL
 FOR ANY DEVICES SHOWN ON PLANS WOULD BE
 PERMITTED AT THIS TIME.
 ** PLEASE KNOW, EQUIPMENT MAY ALWAYS BE
 REVISED.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE COMPLETE PLANS FOR
 PHOTOVOLTAIC SYSTEM. PLEASE SUBMIT ALL
 MANUFACTURES SPECS/ CUT SHEETS FOR
 EQUIPMENT TO BE INSTALLED.
 PLEASE BE SURE ALL SHEETS INDICATE A
 LISTING FROM A NRTL.
 PLEASE BE SURE TO SEE 690 OF THE NEC.
 ** PLEASE BE SURE TO ALSO SEE BLDG
 COMMENTS WITH RESPECT TO WIND LOAD
 CALCULATIONS REQUIRED FOR NEW EQUIPMENT
 BEING INSTALLED ON ROOF.
  
 9) NOTE: NO, PLEASE SEE THIS IS THE SAME
 AS ABOVE. PLEASE SUBMIT AT THIS TIME OR
 KNOW, THE LIGHTING CONTROL SYSTEM CAN BE
 DONE UNDER A SEPARATE PERMIT. NO WIRING
 MAY BE INSTALLED UNTIL THAT PERMIT IS
 ISSUED.
 ** ONCE AGAIN, EQUIPMENT CAN ALWAYS BE
 REVISED.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SUBMIT COMPLETE SPECS/CUT
 SHEETS FOR NEW LIGHTING CONTROL SYSTEM.
 PLEASE BE SURE ALL SHEETS INDICATE A
 LISTING FROM A NRTL.
  
 10) NOTE: OK.
  
 11) NOTE: OK.
  
 12) NOTE: OK, HOWEVER SEE NOTES
 REGARDING LOAD CALCUALTIONS.
  
 13) NOTE:NO, PLEASE SEE LAUNDRY
 CIRCUIT IS SHOWN AT .40VA.
 WASHER REVISED.
  
 ** PREVIOUS PLEASE SEE 220.16, 210.11C2
 FOR MINIMUM VA FOR LAUNDRY AND WASHER.
  
 14) NOTE:OK.
  
 15) NOTE: OK.
  
 16) NOTE: OK.
  
 17) NOTE: NO, PLEASE SEE THESE WERE
 ADDED, HOWEVER PLEASE SEE REDLINED
 PLANS, AS GFI RECEPT IS REQUIRED TO BE
 WITHIN 2' OF THE END/START OF THE
 COUNTERSPACE. ** THIS CAN BE REDLINED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE 210.52C1 FOR KITCHEN
 COUNTER SPACE RECEPTACLES MISSING.
  
 18) NOTE: OK.
  
 19) NOTE: OK.
  
 20) NOTE:NO, PLEASE SEE CALCUALITONS
 WERE SUBMITTED ON PLANS AND IN SPEC
 BOOKS, HOWEVER THEY ARE REFERENCING
 CODES NOT IN THE CURRENT 2002 NEC.
 PLEASE ALSO SEE 220, 220.11 ETC FOR WHAT
 LOADS ARE PERMITTED TO BE DERATED UNDER
 THE TABLE. PLEASE KNOW, NOT ALL LOADS AS
 SHOWN IN LOAD CALCS MAY BE DERATED UNDER
 THE SAME 220.11
 PLEASE KNOW, LOADS MAY BE DONE UNDER
 220.31
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING MINIMUM
 LOAD CALCULATIONS PER NEC.220
  
 21) NOTE: OK.
  
 22) NOTE: NO, RESPONSE MENTIONS THIS IS
 THE LEGAL SIGNATURE, HOWEVER COULD NOT
 LOCATE THE LETTER FROM THE ENGINEER OF
 RECORD. THE LTR WILL BE PLACED IN FILE
 AS PREVIOUSLY NOTED.
  
 ** PREVIUOS REVIEW NOTE **
 PLEASE SEE FS 471.025 WHICH
 REQUIRES THE LEGAL SIGNATURE FOR THE
 ENGINEER OF RECORD. PLANS APPEAR TO
 CONTAIN INITIALS, IF INDEED THIS IS THE
 LEGAL SIGNATURE, PLEASE PROVIDE A
 SIGNED, DATED, SEALED LETTER TO ATTEST
 TO THE LEGAL SIGNATURE. THIS LETTER IS
 REQUIRED TO BE CORRECTLY NOTARIZED UNDER
 FS 117.05
 PLEASE KNOW, THIS WILL GO INTO OUR
 SIGNATURE FILE FOR ANY FUTURE REFERENCED
 NEEDED FOR SIGNATURE.
  
 ** NEW NOTES ***
  
 23) NOTE: PLEASE CLARIFY THE SYMBOL ON
 PLANS AS "SF" AT DOOR LOCATIONS ETC , AS
 THIS DEVICE IS NOT ON SYMBOL LEGEND.
  
 24) NOTE: PLEASE SEE SOME SORT OF
 LIGHTING FIXTURE IS BEING SHOWN IN
 CLOSET WHICH DOES NOT SEEM MIN
 CLEARENCES PER 410.8. PLEASE ALSO SEE
 OTHER TYPE OF FLOURESCENT DOWN LTS,
 WHICH SEEM TO BE DIRECLTY OVER SHELVING
 AREA IN ONE CLOSET.
 PLEASE SUBMIT SPEC/MANUFACTURE CUT
 SHEETS FOR LIGHTING BEING PROPOSED AS
 "STRIP LIGHTING" OF SOME KIND.
 PLEASE SEE 410.8
  
 25) NOTE: PLEASE SEE THE WATER HEATER IS
 BEING SHOWN AS 4.5KW, HOWEVER THE OCP IS
 SHOWN AS 50A'S?
 PLEASE SEE MIN OCP FOR THIS IS 125%,
 HOWEVER MAX OCP IS 150%.(30A) PLEASE
 ALSO SEE CONDUCTOR SIZE SHOWN AT #6
 NEEDS ADJUSTING AS #6 IS NOT RATED UNDER
 THE LUGS OF A 30A BRKR.
 422.11E3
  
 ** PLEASW KNOW, THE DETAILED RESPONSE
 WAS APPRECIATED AS THIS HELPS IN THE
 REVIEW PROCESS.
  
  
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
 ** PLEASE KNOW, IF THIS PERMIT IS GOING
 TO INLCUDE LIGHTING CONTROL SYSTEM AND
 PHOTOVOLTAIC SYSTEM, VALUE FOR COMPLETE
 SCOPE OF WORK WILL BE REQUIRED TO BE
 INCREASED, AS THE VALUES BASED IN THE
 TABLES FOR THE FBC DOES NOT INLCUDE
 THESE SPECIALIZED ELECTRICAL SYSTEMS.
 PLEASE PROVIDE COMPLETE CONTRACT FOR ALL
 TRADES FOR SCOPE OF WORK OR ADJUST VALUE
 IF THESE WILL BE PERMITTED UNDER HOUSE
 PERMIT.
 PLEASE ALOS KNOW, THE ELECTRICAL
 CONTRACTOR UNDER HOUSE PERMIT WILL ALSO
 BE RESPONSIBLE FOR ALL WORK EVEN IF DONE
 BY A SUB CONTRACTOR.
 FBC 108.3
 ** PLEASE HAVE CONTRACTOR CALL TO GO
 OVER.
  