2006-07-16 00:00:00 | IN ELEC FOR REVIEW, FROM ZONING ON 7/11 |
| **** UNSAT **** |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| REVIEW STILL NEED TO BE ADDRESSED. |
| PLEASE ALSO SEE SOME NEW NOTES. |
| |
| ** PLEASE SEE NOTES BELOW ARE TAKEN |
| DIRECTLY FROM PREVIOUS REVIEW AS NOTED, |
| WITH NEW NOTES ADDED TO THE BOTTOM OF |
| THE FIRST REVIEW NOTES. |
| |
| |
| |
| 1) NOTE: OK. |
| |
| 2) NOTE: OK. |
| |
| 3) NOTE: OK. |
| |
| 4) NOTE: OK. |
| |
| 5) NOTE: OK/NO. ADDRESSED COMMENT, |
| HOWEVER DUE TO CHANGES MADE BY COMMENT, |
| PLEASE SEE THE MISPRINT WAS REVISE, |
| HOWEVER PLEASE KNOW, THE CONDUIT |
| EXTENDING FROM GRND TO METER SHALL BE |
| SCHEDULE 80 AS THIS IS AREA IS |
| CONSIDERED SUBMIT TO PHYSICAL DAMAGE. |
| 352.10F |
| |
| ** PREVIOUS REVIEW NOTE**PLEASE SEE |
| UNDERGROUND CONDUITS |
| WHICH MENTIONS THE USE OF SCHEDULE "90" |
| PVC?? PLEASE VERIFY AS THIS IS NOT A |
| COMMON ITEM, NOR IS IT LISTED IN THE |
| NEC. |
| 215.5 |
| |
| 6) NOTE: OK. |
| |
| 7) NOTE: OK. |
| |
| 8) NOTE: NO, PLEASE SEE THIS STILL DOES |
| NOT SEEM TO BE COMPLETE AT THIS TIME FOR |
| INTENDED LOADS, DISCONNECTING MEANS ECT. |
| PLEASE ALSO SEE THAT MANUFACTURES |
| SPECS/CUT SHEETS WERE NOT SUBMITTED. |
| PLEASE KNOW, IT IS NOTED THAT THE |
| RESPONSE MENTIONS THIS WOULD BE DONE AT |
| A LATER DATE , HOWEVER THIS IS REQUIRED |
| AT THIS TIME IF SYSTEM IS GOING TO BE |
| UNDER MAIN HOUSE PERMIT. PLEASE SEE |
| PLANS ARE NOT DETAILED ENOUGH FOR |
| TRANSFER OF POWER AND WHERE THAT IS |
| TAKING PLACE, DISCONNECTING MEANS ETC. |
| ** PLEASE KNOW, THE PV SYSTEM MAY |
| EXCLUDED AND SUBMITTED UNDER A SEPARATE |
| PERMIT AT A LATER DATE. NO ELECTRICAL |
| FOR ANY DEVICES SHOWN ON PLANS WOULD BE |
| PERMITTED AT THIS TIME. |
| ** PLEASE KNOW, EQUIPMENT MAY ALWAYS BE |
| REVISED. |
| |
| ** PREVIOUS REVIEW NOTE** |
| PLEASE COMPLETE PLANS FOR |
| PHOTOVOLTAIC SYSTEM. PLEASE SUBMIT ALL |
| MANUFACTURES SPECS/ CUT SHEETS FOR |
| EQUIPMENT TO BE INSTALLED. |
| PLEASE BE SURE ALL SHEETS INDICATE A |
| LISTING FROM A NRTL. |
| PLEASE BE SURE TO SEE 690 OF THE NEC. |
| ** PLEASE BE SURE TO ALSO SEE BLDG |
| COMMENTS WITH RESPECT TO WIND LOAD |
| CALCULATIONS REQUIRED FOR NEW EQUIPMENT |
| BEING INSTALLED ON ROOF. |
| |
| 9) NOTE: NO, PLEASE SEE THIS IS THE SAME |
| AS ABOVE. PLEASE SUBMIT AT THIS TIME OR |
| KNOW, THE LIGHTING CONTROL SYSTEM CAN BE |
| DONE UNDER A SEPARATE PERMIT. NO WIRING |
| MAY BE INSTALLED UNTIL THAT PERMIT IS |
| ISSUED. |
| ** ONCE AGAIN, EQUIPMENT CAN ALWAYS BE |
| REVISED. |
| |
| ** PREVIOUS REVIEW NOTE** |
| PLEASE SUBMIT COMPLETE SPECS/CUT |
| SHEETS FOR NEW LIGHTING CONTROL SYSTEM. |
| PLEASE BE SURE ALL SHEETS INDICATE A |
| LISTING FROM A NRTL. |
| |
| 10) NOTE: OK. |
| |
| 11) NOTE: OK. |
| |
| 12) NOTE: OK, HOWEVER SEE NOTES |
| REGARDING LOAD CALCUALTIONS. |
| |
| 13) NOTE:NO, PLEASE SEE LAUNDRY |
| CIRCUIT IS SHOWN AT .40VA. |
| WASHER REVISED. |
| |
| ** PREVIOUS PLEASE SEE 220.16, 210.11C2 |
| FOR MINIMUM VA FOR LAUNDRY AND WASHER. |
| |
| 14) NOTE:OK. |
| |
| 15) NOTE: OK. |
| |
| 16) NOTE: OK. |
| |
| 17) NOTE: NO, PLEASE SEE THESE WERE |
| ADDED, HOWEVER PLEASE SEE REDLINED |
| PLANS, AS GFI RECEPT IS REQUIRED TO BE |
| WITHIN 2' OF THE END/START OF THE |
| COUNTERSPACE. ** THIS CAN BE REDLINED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE 210.52C1 FOR KITCHEN |
| COUNTER SPACE RECEPTACLES MISSING. |
| |
| 18) NOTE: OK. |
| |
| 19) NOTE: OK. |
| |
| 20) NOTE:NO, PLEASE SEE CALCUALITONS |
| WERE SUBMITTED ON PLANS AND IN SPEC |
| BOOKS, HOWEVER THEY ARE REFERENCING |
| CODES NOT IN THE CURRENT 2002 NEC. |
| PLEASE ALSO SEE 220, 220.11 ETC FOR WHAT |
| LOADS ARE PERMITTED TO BE DERATED UNDER |
| THE TABLE. PLEASE KNOW, NOT ALL LOADS AS |
| SHOWN IN LOAD CALCS MAY BE DERATED UNDER |
| THE SAME 220.11 |
| PLEASE KNOW, LOADS MAY BE DONE UNDER |
| 220.31 |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE MISSING MINIMUM |
| LOAD CALCULATIONS PER NEC.220 |
| |
| 21) NOTE: OK. |
| |
| 22) NOTE: NO, RESPONSE MENTIONS THIS IS |
| THE LEGAL SIGNATURE, HOWEVER COULD NOT |
| LOCATE THE LETTER FROM THE ENGINEER OF |
| RECORD. THE LTR WILL BE PLACED IN FILE |
| AS PREVIOUSLY NOTED. |
| |
| ** PREVIUOS REVIEW NOTE ** |
| PLEASE SEE FS 471.025 WHICH |
| REQUIRES THE LEGAL SIGNATURE FOR THE |
| ENGINEER OF RECORD. PLANS APPEAR TO |
| CONTAIN INITIALS, IF INDEED THIS IS THE |
| LEGAL SIGNATURE, PLEASE PROVIDE A |
| SIGNED, DATED, SEALED LETTER TO ATTEST |
| TO THE LEGAL SIGNATURE. THIS LETTER IS |
| REQUIRED TO BE CORRECTLY NOTARIZED UNDER |
| FS 117.05 |
| PLEASE KNOW, THIS WILL GO INTO OUR |
| SIGNATURE FILE FOR ANY FUTURE REFERENCED |
| NEEDED FOR SIGNATURE. |
| |
| ** NEW NOTES *** |
| |
| 23) NOTE: PLEASE CLARIFY THE SYMBOL ON |
| PLANS AS "SF" AT DOOR LOCATIONS ETC , AS |
| THIS DEVICE IS NOT ON SYMBOL LEGEND. |
| |
| 24) NOTE: PLEASE SEE SOME SORT OF |
| LIGHTING FIXTURE IS BEING SHOWN IN |
| CLOSET WHICH DOES NOT SEEM MIN |
| CLEARENCES PER 410.8. PLEASE ALSO SEE |
| OTHER TYPE OF FLOURESCENT DOWN LTS, |
| WHICH SEEM TO BE DIRECLTY OVER SHELVING |
| AREA IN ONE CLOSET. |
| PLEASE SUBMIT SPEC/MANUFACTURE CUT |
| SHEETS FOR LIGHTING BEING PROPOSED AS |
| "STRIP LIGHTING" OF SOME KIND. |
| PLEASE SEE 410.8 |
| |
| 25) NOTE: PLEASE SEE THE WATER HEATER IS |
| BEING SHOWN AS 4.5KW, HOWEVER THE OCP IS |
| SHOWN AS 50A'S? |
| PLEASE SEE MIN OCP FOR THIS IS 125%, |
| HOWEVER MAX OCP IS 150%.(30A) PLEASE |
| ALSO SEE CONDUCTOR SIZE SHOWN AT #6 |
| NEEDS ADJUSTING AS #6 IS NOT RATED UNDER |
| THE LUGS OF A 30A BRKR. |
| 422.11E3 |
| |
| ** PLEASW KNOW, THE DETAILED RESPONSE |
| WAS APPRECIATED AS THIS HELPS IN THE |
| REVIEW PROCESS. |
| |
| |
| |
| ** PLEASE SEE ANY OTHER COMMENTS FROM |
| OTHER REVIEWER(S) WHICH MAY AFFECT |
| ELECTRICAL PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW. |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| ** PLEASE KNOW, IF THIS PERMIT IS GOING |
| TO INLCUDE LIGHTING CONTROL SYSTEM AND |
| PHOTOVOLTAIC SYSTEM, VALUE FOR COMPLETE |
| SCOPE OF WORK WILL BE REQUIRED TO BE |
| INCREASED, AS THE VALUES BASED IN THE |
| TABLES FOR THE FBC DOES NOT INLCUDE |
| THESE SPECIALIZED ELECTRICAL SYSTEMS. |
| PLEASE PROVIDE COMPLETE CONTRACT FOR ALL |
| TRADES FOR SCOPE OF WORK OR ADJUST VALUE |
| IF THESE WILL BE PERMITTED UNDER HOUSE |
| PERMIT. |
| PLEASE ALOS KNOW, THE ELECTRICAL |
| CONTRACTOR UNDER HOUSE PERMIT WILL ALSO |
| BE RESPONSIBLE FOR ALL WORK EVEN IF DONE |
| BY A SUB CONTRACTOR. |
| FBC 108.3 |
| ** PLEASE HAVE CONTRACTOR CALL TO GO |
| OVER. |
| |