Plan Review Notes For Permit 06030523
Permit Number 06030523
Review Stop P
Sequence Number 1
Notes
Date Text
2006-03-21 00:00:00DENIED;
 1.SHOW SIZE OF ROOF AREA TO DRAIN TO
 STORAGE TANK, AND SIZE ALL HORIZONTAL
 PIPING. SEE FBC-2004 PLUMBING TABLE
 1106.3.ALSO SHOW SIZE OF ROOF GUTTERS
 AND DOWN SPOUTS.
 2.A/C CONDENSATE IS NOT PERMITED TO GO
 TO SANITARY SEWER. UTILITY ORD. INSTALL
 A DRY WELL FOR CONDENSATE.
 3.SANITARY RISER DIAGRAM IS REQUIRED SEE
 WPB AMENDMENTS TO THE FBC CHAPTER 1,
 SEC106.3.5.4(9)
 4. HORIZONTAL DRY VENTS ARE NOT PERMITED
 IN THE SANITARY DRAINAGE SYSTEM. SEE
 GARAGE FLOOR DRAINS, BIDET, ETC. SEC.
 905.3.
 5.FLOOR DRAINS IN GARAGE AREA MAY
 REQUIRE A SAND AND OIL SEPARATOR. MORE
 DETAIL REQUIRED WHY ARE TWO FLOOR DRAINS
 NEEDED IN GARAGE?
 6.SEE TABLE 704.1 FOR THE MINIMUM SLOPE
 OF HORIZONTAL DRAINAGE PIPE.
 7.PLEASE SHOW A DETAIL OF WATER HEATER
 ASSEMBY. NOT ENOUGH DETAILS. COULD NOT
 FIND MEP SPECIFCATIONS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695