2006-03-20 00:00:00 | |
| ******* UNSAT ******** |
| |
| 1) NOTE: PLEASE ADD NOTE WHICH STATES |
| THAT THE LIGHTNING PROTECTION SYSTEM |
| SHALL BE UNDER A SEPARATE PERMIT. |
| |
| 2) NOTE: PLEASE CLARIFY PANEL 1B AND 1C, |
| AS THESE ARE SHOWN WITH ?FEED-THRU? |
| LUGS? ARE THERE OTHER PANELS? |
| 215.5 |
| |
| 3) NOTE: PLEASE SEE 250.6, 250.24B, |
| RISER DIAGRAM SHOWS "EQUIPMENT GROUNDING |
| CONDUCTORS" FROM FPL TO THE FIRST MEANS |
| OF DISCONNECT. PLEASE KNOW, THE |
| "EQUIPMENT GRND" SHOULD ONLY BE |
| INSTALLED AFTER THE FIRST MEANS OF |
| DISCONNECT. |
| |
| 4) NOTE: PLEASE CLARIFY USE OF WHAT |
| APPEARS TO BE A "CT" FOR METERING. THIS |
| IS UNCLEAR AS THE PLANS INDICATE A |
| METER, BUT THE PLANS DO NOT SHOW A METER |
| ON HOUSE? |
| IF A CT IS NOT USED, PLEASE INCLUDE |
| METER CAN ON RISER AND ADJUST CONDUCTORS |
| ETC. |
| PLEASE OBTAIN A LETTER FROM AN FPL |
| SERVICE PLANNER, WHICH STATES THAT A |
| "CT" IS GOING TO BE USED. |
| |
| 5) NOTE: PLEASE SEE UNDERGROUND CONDUITS |
| WHICH MENTIONS THE USE OF SCHEDULE "90" |
| PVC?? PLEASE VERIFY AS THIS IS NOT A |
| COMMON ITEM, NOR IS IT LISTED IN THE |
| NEC. |
| 215.5 |
| |
| 6) NOTE: PLEASE VERIFY THE MIN DEPTH OF |
| UNDER GROUND SERVICE ENTRANCE CONDUITS. |
| PLEASE SEE THE MIN DEPTH PER FPL GUIDE |
| LINES IS 24INCHES TO THE TOP OF THE |
| CONDUITS. |
| PLEASE ALSO SEE NOTE/DETAIL MENTIONS |
| 18INCHES UNDER ROADS? PLEASE SEE 300.5 |
| FOR MIN |
| DEPTHS. |
| |
| 7) NOTE: PLEASE SEE MINIMUM GROUNDING |
| ELECTRODE SYSTEM TO BE SHOWN PER |
| 250.50,250.52 |
| PLEASE INCLUDE, CWP, FOOTER STEEL, AT A |
| MIN. |
| |
| 8) NOTE: PLEASE COMPLETE PLANS FOR |
| PHOTOVOLTAIC SYSTEM. PLEASE SUBMIT ALL |
| MANUFACTURES SPECS/ CUT SHEETS FOR |
| EQUIPMENT TO BE INSTALLED. |
| PLEASE BE SURE ALL SHEETS INDICATE A |
| LISTING FROM A NRTL. |
| PLEASE BE SURE TO SEE 690 OF THE NEC. |
| ** PLEASE BE SURE TO ALSO SEE BLDG |
| COMMENTS WITH RESPECT TO WIND LOAD |
| CALCULATIONS REQUIRED FOR NEW EQUIPMENT |
| BEING INSTALLED ON ROOF. |
| |
| 9) NOTE: PLEASE SUBMIT COMPLETE |
| SPECS/CUT SHEETS FOR NEW LIGHTING |
| CONTROL SYSTEM. PLEASE BE SURE ALL |
| SHEETS INDICATE A LISTING FROM A NRTL. |
| |
| 10) NOTE: PLEASE SEE 2002 NEC 210.12B |
| FOR MIN ARC FAULT PROTECTION REQUIRED |
| FOR ALL OUTLETS IN SLEEPING ROOMS. |
| PLEASE SEE THIS INCLUDES, LIGHTS, |
| RECEPTS, SD'S, FANS ETC. PLEASE VERIFY |
| THE PROTECTION AND HOW THESE WILL BE |
| TIED INTO LIGHTING CONTROL SYSTEMS. |
| |
| 11) NOTE: PLEASE SEE NFPA-72 11.5.1.1 |
| WHICH REQUIRES A SD ON EACH LEVEL OF A |
| MULTI-LEVEL BUILDING IN THE IMMEDIATE |
| VICINITY OF STAIRS LEADING TO THE FLOOR |
| ABOVE. |
| |
| 12) NOTE: PLEASE MININUM VA REQUIRED |
| FOR SMALL APPL CIRCUITS PER 220.12, |
| 210.52B1,210.11C1 |
| |
| 13) NOTE: PLEASE SEE 220.12, 210.11C2 |
| FOR MINIMUM VA FOR LAUNDRY AND WASHER. |
| |
| 14) NOTE: PLEASE SEE 220.18 FOR MINIMUM |
| VA FOR DRYER LOADS. |
| |
| 15) NOTE: PLEASE SEE 210.8A7 FOR ALL |
| RECEPTS LOCATED WITHIN 6 FT OF A SINK TO |
| BE GFI/ GFI PROTECTED. |
| UPPER LAUNDRY ROOM. |
| |
| 16) NOTE: PLEASE SEE KEY NOTE P2 WHICH |
| STATES ALL OUTSIDE GFI RECEPTS TO BE |
| HALF SWITCHED. PLEASE KNOW, THIS IS NOT |
| POSSIBLE AS GFI RECEPTS ARE NOT MADE TO |
| BE HALF SWITCH. THERE ARE ONLY LINE OR |
| LOAD CONNECTIONS. |
| PLEASE SEE 210.52E FOR MINIMUM REQUIRED. |
| |
| 17) NOTE: PLEASE 210.52C1 FOR KITCHEN |
| COUNTER SPACE RECEPTACLES MISSING. |
| |
| 18) NOTE: PLEASE SEE MISSING CIRCUITING |
| FOR SD'S. |
| 215.5 |
| |
| 19) NOTE: PLEASE SEE PANEL "A" IS |
| MISSING LOADS FOR PANEL "C". |
| 215.5 |
| |
| 20) NOTE: PLEASE SEE MISSING MINIMUM |
| LOAD CALCULATIONS PER NEC.220 |
| |
| 21) NOTE: PLEASE MAKE REFERENCE TO THE |
| FOLLOWING CURRENT CODES IN EFFECT. 2002 |
| NFPA-70, 2002 NFPA-72 |
| |
| 22) NOTE: PLEASE SEE FS 471.025 WHICH |
| REQUIRES THE LEGAL SIGNATURE FOR THE |
| ENGINEER OF RECORD. PLANS APPEAR TO |
| CONTAIN INITIALS, IF INDEED THIS IS THE |
| LEGAL SIGNATURE, PLEASE PROVIDE A |
| SIGNED, DATED, SEALED LETTER TO ATTEST |
| TO THE LEGAL SIGNATURE. THIS LETTER IS |
| REQUIRED TO BE CORRECTLY NOTARIZED UNDER |
| FS 117.05 |
| PLEASE KNOW, THIS WILL GO INTO OUR |
| SIGNATURE FILE FOR ANY FUTURE REFERENCED |
| NEEDED FOR SIGNATURE. |
| |
| ** PLEASE SEE ANY OTHER COMMENTS FROM |
| OTHER REVIEWER(S) WHICH MAY AFFECT |
| ELECTRICAL PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW. |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
2006-03-18 00:00:00 | IN ELEC FOR REVIEW. |
| REVIEW STOPPED. WILL CONTINUE ON 3/20 |
| NOTES TO FOLLOW. |