Plan Review Notes
Plan Review Notes For Permit 06030523
Permit Number 06030523
Review Stop E
Sequence Number 1
Notes
Date Text
2006-03-20 00:00:00 
 ******* UNSAT ********
  
 1) NOTE: PLEASE ADD NOTE WHICH STATES
 THAT THE LIGHTNING PROTECTION SYSTEM
 SHALL BE UNDER A SEPARATE PERMIT.
  
 2) NOTE: PLEASE CLARIFY PANEL 1B AND 1C,
 AS THESE ARE SHOWN WITH ?FEED-THRU?
 LUGS? ARE THERE OTHER PANELS?
 215.5
  
 3) NOTE: PLEASE SEE 250.6, 250.24B,
 RISER DIAGRAM SHOWS "EQUIPMENT GROUNDING
 CONDUCTORS" FROM FPL TO THE FIRST MEANS
 OF DISCONNECT. PLEASE KNOW, THE
 "EQUIPMENT GRND" SHOULD ONLY BE
 INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 4) NOTE: PLEASE CLARIFY USE OF WHAT
 APPEARS TO BE A "CT" FOR METERING. THIS
 IS UNCLEAR AS THE PLANS INDICATE A
 METER, BUT THE PLANS DO NOT SHOW A METER
 ON HOUSE?
 IF A CT IS NOT USED, PLEASE INCLUDE
 METER CAN ON RISER AND ADJUST CONDUCTORS
 ETC.
 PLEASE OBTAIN A LETTER FROM AN FPL
 SERVICE PLANNER, WHICH STATES THAT A
 "CT" IS GOING TO BE USED.
  
 5) NOTE: PLEASE SEE UNDERGROUND CONDUITS
 WHICH MENTIONS THE USE OF SCHEDULE "90"
 PVC?? PLEASE VERIFY AS THIS IS NOT A
 COMMON ITEM, NOR IS IT LISTED IN THE
 NEC.
 215.5
  
 6) NOTE: PLEASE VERIFY THE MIN DEPTH OF
 UNDER GROUND SERVICE ENTRANCE CONDUITS.
 PLEASE SEE THE MIN DEPTH PER FPL GUIDE
 LINES IS 24INCHES TO THE TOP OF THE
 CONDUITS.
 PLEASE ALSO SEE NOTE/DETAIL MENTIONS
 18INCHES UNDER ROADS? PLEASE SEE 300.5
 FOR MIN
 DEPTHS.
  
 7) NOTE: PLEASE SEE MINIMUM GROUNDING
 ELECTRODE SYSTEM TO BE SHOWN PER
 250.50,250.52
 PLEASE INCLUDE, CWP, FOOTER STEEL, AT A
 MIN.
  
 8) NOTE: PLEASE COMPLETE PLANS FOR
 PHOTOVOLTAIC SYSTEM. PLEASE SUBMIT ALL
 MANUFACTURES SPECS/ CUT SHEETS FOR
 EQUIPMENT TO BE INSTALLED.
 PLEASE BE SURE ALL SHEETS INDICATE A
 LISTING FROM A NRTL.
 PLEASE BE SURE TO SEE 690 OF THE NEC.
 ** PLEASE BE SURE TO ALSO SEE BLDG
 COMMENTS WITH RESPECT TO WIND LOAD
 CALCULATIONS REQUIRED FOR NEW EQUIPMENT
 BEING INSTALLED ON ROOF.
  
 9) NOTE: PLEASE SUBMIT COMPLETE
 SPECS/CUT SHEETS FOR NEW LIGHTING
 CONTROL SYSTEM. PLEASE BE SURE ALL
 SHEETS INDICATE A LISTING FROM A NRTL.
  
 10) NOTE: PLEASE SEE 2002 NEC 210.12B
 FOR MIN ARC FAULT PROTECTION REQUIRED
 FOR ALL OUTLETS IN SLEEPING ROOMS.
 PLEASE SEE THIS INCLUDES, LIGHTS,
 RECEPTS, SD'S, FANS ETC. PLEASE VERIFY
 THE PROTECTION AND HOW THESE WILL BE
 TIED INTO LIGHTING CONTROL SYSTEMS.
  
 11) NOTE: PLEASE SEE NFPA-72 11.5.1.1
 WHICH REQUIRES A SD ON EACH LEVEL OF A
 MULTI-LEVEL BUILDING IN THE IMMEDIATE
 VICINITY OF STAIRS LEADING TO THE FLOOR
 ABOVE.
  
 12) NOTE: PLEASE MININUM VA REQUIRED
 FOR SMALL APPL CIRCUITS PER 220.12,
 210.52B1,210.11C1
  
 13) NOTE: PLEASE SEE 220.12, 210.11C2
 FOR MINIMUM VA FOR LAUNDRY AND WASHER.
  
 14) NOTE: PLEASE SEE 220.18 FOR MINIMUM
 VA FOR DRYER LOADS.
  
 15) NOTE: PLEASE SEE 210.8A7 FOR ALL
 RECEPTS LOCATED WITHIN 6 FT OF A SINK TO
 BE GFI/ GFI PROTECTED.
 UPPER LAUNDRY ROOM.
  
 16) NOTE: PLEASE SEE KEY NOTE P2 WHICH
 STATES ALL OUTSIDE GFI RECEPTS TO BE
 HALF SWITCHED. PLEASE KNOW, THIS IS NOT
 POSSIBLE AS GFI RECEPTS ARE NOT MADE TO
 BE HALF SWITCH. THERE ARE ONLY LINE OR
 LOAD CONNECTIONS.
 PLEASE SEE 210.52E FOR MINIMUM REQUIRED.
  
 17) NOTE: PLEASE 210.52C1 FOR KITCHEN
 COUNTER SPACE RECEPTACLES MISSING.
  
 18) NOTE: PLEASE SEE MISSING CIRCUITING
 FOR SD'S.
 215.5
  
 19) NOTE: PLEASE SEE PANEL "A" IS
 MISSING LOADS FOR PANEL "C".
 215.5
  
 20) NOTE: PLEASE SEE MISSING MINIMUM
 LOAD CALCULATIONS PER NEC.220
  
 21) NOTE: PLEASE MAKE REFERENCE TO THE
 FOLLOWING CURRENT CODES IN EFFECT. 2002
 NFPA-70, 2002 NFPA-72
  
 22) NOTE: PLEASE SEE FS 471.025 WHICH
 REQUIRES THE LEGAL SIGNATURE FOR THE
 ENGINEER OF RECORD. PLANS APPEAR TO
 CONTAIN INITIALS, IF INDEED THIS IS THE
 LEGAL SIGNATURE, PLEASE PROVIDE A
 SIGNED, DATED, SEALED LETTER TO ATTEST
 TO THE LEGAL SIGNATURE. THIS LETTER IS
 REQUIRED TO BE CORRECTLY NOTARIZED UNDER
 FS 117.05
 PLEASE KNOW, THIS WILL GO INTO OUR
 SIGNATURE FILE FOR ANY FUTURE REFERENCED
 NEEDED FOR SIGNATURE.
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
2006-03-18 00:00:00IN ELEC FOR REVIEW.
 REVIEW STOPPED. WILL CONTINUE ON 3/20
 NOTES TO FOLLOW.