2007-02-06 16:19:15DENIED FIFTH TIME
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING ITEMS ARE STILL REQUIRED TO BE CORRECTED
 FOR PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET P-1 AND P-2 SANITARY ISOMETRICS AND PLUMBING
 PLAN WASHING MACHINE BRANCH DRAINS ARE STILL SIZED
 WRONG ON ALL UNITS ( 708 FIRST AND SECOND FLOOR, 708
 1/2A AND 708 1/2B) PER FBC-2004 PLUMBING, SECTION 406.3
 THEY NEED TO BE THREE INCH (3") NOT TWO INCH (2").
 PLEASE CORRECT AND RESUBMIT.
  
 2. SEE ATTACHED NOTICE FS 553.80 (2) (B) REGAURDING
 FOUR TIMES THE FEE.
  
 THE FOLLWING ARE NEW ITEMS THAT NEED TO BE CORRECTED
 FOR PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 3. SHEET P-1 GENERAL NOTES #16 DELETE "APPROVED AIR
 CHAMBERS" AND ADD IN ITS PLACE THE FOLLOWING " WATER
 HAMMER ARRESTORS TO BE INSTALLED PER FBC-2004 PLUMBING,
 SECTION 604.9."
  
 4. SHEET P-1 NOTE ON TUB AND SHOWER VALVES: PLEASE ADD
 "TUB AND SHOWER VALVES TO BE INSTALLED PER FBC-2004
 PLUMBING, SECTION 424.3.
  
 5. SHEET P-2 UNIT 708 1/2A WATER ISOMETRIC: A} PER
 FBC-2004 PLUMBING, SECTION 606.1 (2) FULL-OPEN VALVE
 REQUIRED ON THE WATER DISTRIBUTION SUPPLY PIPE AT THE
 ENTRANCE INTO THE BUILDING. B} HOT AND COLD WATER ARE
 CROSSED ON THE WASHER, KITCHEN, AND LAV, PER FBC-2004
 PLUMBING SECTION 607.4 FLOW OF HOT WATER TO FIXTURES
 SHALL BE INSTALLED AND ADJUSTED SO THAT THE FLOW OF HOT
 WATER FROM THE FITTING CORRESPONDS TO THE LEFT-SIDE OF
 THE FIXTURE FITTING. C} WATER SERVICE NEEDS TO SUPPLY
 THE WATER DISTRIBUTION PIPING FIRST THEN BRANCH TO THE
 WATER HEATER AS THE CORRECTED DRAWING INDICATES, NOT
 DIRECTLY SUPPLY THE WATER HEATER AS SHOWN. PLEASE
 CORRECT AND RESUBMIT. D} PLEASE CLARIFY THE THIRD WATER
 CONNECTION TO THE WASHER. IS IT NEEDED, IF NOT PLEASE
 DELETE.
  
 6. SHEET P-2 708 1/2B WATER ISOMETRIC: A} PER FBC-2004
 PLUMBING, SECTION 606.1 (2) FULL-OPEN VALVE REQUIRED ON
 THE WATER DISTRIBUTION SUPPLY PIPE AT THE ENTRANCE INTO
 THE BUILDING. B} HOT AND COLD WATER ARE CROSSED ON THE
 LAV AND WASHER, PER FBC-2004 PLUMBING SECTION 607.4
 FLOW OF HOT WATER TO FIXTURES SHALL BE INSTALLED AND
 ADJUSTED SO THAT THE FLOW OF HOT WATER FROM THE FITTING
 CORRESPONDS TO THE LEFT-SIDE OF THE FIXTURE FITTING. C}
 WATER SERVICE NEEDS TO SUPPLY THE WATER DISTRIBUTION
 PIPING FIRST THEN BRANCH TO THE WATER HEATER AS THE
 CORRECTED DRAWING INDICATES, NOT DIRECTLY SUPPLY THE
 WATER HEATER AS SHOWN. PLEASE CORRECT AND RESUBMIT. D}
 IS IT THE INTENT TO HAVE HOT WATER SUPPLIED TO THE HOSE
 BIBB AS INDICATED. IF NOT PLEASE CORRECT AND RESUBMIT.
 E} PLEASE CLARIFY THE THIRD WATER CONNECTION TO THE
 WASHER. IS IT NEEDED, IF NOT PLEASE DELETE.
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  