Plan Review Notes For Permit 06030498 |
Permit Number |
06030498 |
|
Review Stop |
E |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2007-02-01 11:51:38 | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} LOCATE THE SERVICE DISCONNECTS ON THE PLAN. THE | | LOCATION OF THE METER DOES NOT APPEAR TO LEAVE ROOM | | (PHYSICALLY) FOR THE DISCONNECTS SHOWN (AND REQUIRED) | | ON THE RISER, AT THE SAME LOCATION. ALSO NOTE THE | | SERVICE DROP CONDUCTORS CANNOT BE WITHIN 3' OF THE 2ND | | FLOOR WINDOW. SEE SHEET A-4. | | | | 2} PLEASE INDICATE THE MAIN BREAKER RATING ON THE | | DISCONNECTS. 215.5. | | | | 3} PLACING THE CONDENSING UNITS AND THEIR DISCONNECTS | | UNDER THE STEPS VIOLATES 110.26 CLEARANCE REQUIREMENTS, | | SEE NOTE #15, E-1. | | | | 4} PER ZONING CODE THE RANGE CIRCUIT MUST BE REMOVED | | FROM THE CALCULATIONS AND THE PANEL SCHEDULE FOR THE | | SECOND FLOOR. | | | | 5} PLEASE EXPLAIN WHY THE "INSTA HOT" WATER HEATERS ARE | | CALCULATED AT 2VA IN THE CALCS.. | | | | 6} PANEL SCHEDULE "B"DOES NOT SHOW CIRCUITING FOR THE | | BAR OR MEDIA, BUT DOES SHOW CIRCUITS FOR THE DINING | | ROOM AND SMALL APPLIANCES, THAT ARE NOT ON THAT FLOOR. | | PLEASE CORRELATE THE SCHEDULE WITH THE FLOOR PLAN. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|