Plan Review Notes
Plan Review Notes For Permit 06030498
Permit Number 06030498
Review Stop E
Sequence Number 5
Notes
Date Text
2007-02-01 11:51:38 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} LOCATE THE SERVICE DISCONNECTS ON THE PLAN. THE
 LOCATION OF THE METER DOES NOT APPEAR TO LEAVE ROOM
 (PHYSICALLY) FOR THE DISCONNECTS SHOWN (AND REQUIRED)
 ON THE RISER, AT THE SAME LOCATION. ALSO NOTE THE
 SERVICE DROP CONDUCTORS CANNOT BE WITHIN 3' OF THE 2ND
 FLOOR WINDOW. SEE SHEET A-4.
  
 2} PLEASE INDICATE THE MAIN BREAKER RATING ON THE
 DISCONNECTS. 215.5.
  
 3} PLACING THE CONDENSING UNITS AND THEIR DISCONNECTS
 UNDER THE STEPS VIOLATES 110.26 CLEARANCE REQUIREMENTS,
 SEE NOTE #15, E-1.
  
 4} PER ZONING CODE THE RANGE CIRCUIT MUST BE REMOVED
 FROM THE CALCULATIONS AND THE PANEL SCHEDULE FOR THE
 SECOND FLOOR.
  
 5} PLEASE EXPLAIN WHY THE "INSTA HOT" WATER HEATERS ARE
 CALCULATED AT 2VA IN THE CALCS..
  
 6} PANEL SCHEDULE "B"DOES NOT SHOW CIRCUITING FOR THE
 BAR OR MEDIA, BUT DOES SHOW CIRCUITS FOR THE DINING
 ROOM AND SMALL APPLIANCES, THAT ARE NOT ON THAT FLOOR.
 PLEASE CORRELATE THE SCHEDULE WITH THE FLOOR PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]