Plan Review Notes For Permit 06030498 |
Permit Number |
06030498 |
|
Review Stop |
P |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2006-12-26 15:14:35 | DENIED 4TH TIME | | REFERENCE: FBC-2004 PLUMBING | | | | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING | | PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | 1. SHEET NO. SP-1 PLUMBING NOTES PLEASE CHANGE | | "PROVIDE A MINIMUM PITCH OF 1/8 INCH AT ALL HORIZONTAL | | BRANCHES AND SEWER LINES" TO READ "SLOPE OF HORIZONTAL | | DRAINAGE PIPE PER TABLE 704.1". | | | | 2. SHEETS P-1 AND P-2 THE FOLLOWING IS REQUIRED FOR | | THE WASHING MACHINES PER FBC-2004 PLUMBING, SEC. 406.3. | | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND | | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES | | WASHER SHALL BE A MINIMUM OF 2 INCHES | | (51MM) IN DIAMETER. THE AUTOMATIC | | CLOTHES WASHER FIXTURE DRAIN SHALL | | CONNECT TO A BRANCH DRAIN OR DRAINAGE | | STACK A MINIMUM OF 3 INCHES (76MM) IN | | DIAMETER. | | | | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, | | PLEASE REPLACE ONLY SHEETS | | WHICH HAVE CHANGED AND PROVIDE ONE COPY | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | ONLY. NOTE: ONLY ONE CORRECTED DRAWING | | IN RED INK FOR REFERENCE FOR | | RESUBMITTAL. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561) 805-6721 |
|