2006-12-22 13:58:31 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 COMMENTS, SHEET E-1.
  
 1} THE GEC IS TOO SMALL FOR THE SERVICE CONDUCTORS. SEE
 250.66, MINIMUM #2.
  
 2} THE #1 CU FEEDERS FROM THE 200 AMP METER/MAINS IS
 TOO SMALL PER 310.15(B)(6), 2/0 MINIMUM.
  
 3} THE EQUIPMENT GROUND RAN WITH THE FEEDERS IS IN
 VIOLATION OF 250.122, NEEDS TO BE #6 MIN.
  
 4} THE BATH CIRCUITS IN ALL PANELS MUST BE ON THEIR OWN
 CIRCUIT PER 210.11(C)(3).
  
 5} NOTE #14 ON BOTH SHEETS SHOULD ALSO INDICATE THE
 DETECTOR CIRCUIT MUST BE ARC FAULT PER 210.12.
  
 6} THE #2FEEDERS ON E-2 ARE TOO SMALL FOR A 150 AMP
 OCP PER 310.15.BOTH SERVICES.
  
 7} THE TITLE BLOCK INDICATING "ARCHITECTURAL SERVICES"
 MUST CONTAIN A CERTIFICATE OF AUTHORIZATION PER 481
 FS..
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]