Plan Review Notes For Permit 06030498 |
Permit Number |
06030498 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2006-12-22 13:58:31 | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | COMMENTS, SHEET E-1. | | | | 1} THE GEC IS TOO SMALL FOR THE SERVICE CONDUCTORS. SEE | | 250.66, MINIMUM #2. | | | | 2} THE #1 CU FEEDERS FROM THE 200 AMP METER/MAINS IS | | TOO SMALL PER 310.15(B)(6), 2/0 MINIMUM. | | | | 3} THE EQUIPMENT GROUND RAN WITH THE FEEDERS IS IN | | VIOLATION OF 250.122, NEEDS TO BE #6 MIN. | | | | 4} THE BATH CIRCUITS IN ALL PANELS MUST BE ON THEIR OWN | | CIRCUIT PER 210.11(C)(3). | | | | 5} NOTE #14 ON BOTH SHEETS SHOULD ALSO INDICATE THE | | DETECTOR CIRCUIT MUST BE ARC FAULT PER 210.12. | | | | 6} THE #2FEEDERS ON E-2 ARE TOO SMALL FOR A 150 AMP | | OCP PER 310.15.BOTH SERVICES. | | | | 7} THE TITLE BLOCK INDICATING "ARCHITECTURAL SERVICES" | | MUST CONTAIN A CERTIFICATE OF AUTHORIZATION PER 481 | | FS.. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|