2007-02-07 11:43:12*** DENIED ***
 SEE MECHANICAL PLAN PAGE M-1.
  
 1) UNIT 708 1ST. FL. BEDROOM 1, RETURN AIR TRANSFER
 DUCT IS LISTED AS A RETURN AIR TRANSFER GRILL, PLEASE
 CORRECT.
  
 2) SAME UNIT PLEASE SHOW SIZE OF RETURN AIR TRANSFER
 DUCT (FLEX).
  
 3) UNIT 708 2ND. FL., ALL RETURN AIR TRANSFER DUCTS ARE
 LISTED AS RETURN AIR TRANSFER GRILLS, PLEASE CORRECT.
  
 4) SAME UNIT, PLEASE SHOW SIZE OF RETURN AIR TRANSFER
 DUCTS (FLEX).
  
 5) UNIT 708 -1/2 A,ALL RETURN AIR TRANSFER DUCTS ARE
 LISTED AS RETURN AIR TRANSFER GRILLS, PLEASE CORRECT.
  
 6) SAME UNIT, 7" RETURN AIR TRANSFER DUCTS (FLEX) ARE
 UNDER SIZED FOR BEDROOMS, BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR
 SPACE IT'S SERVING AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE PROPER RETURN
 AIR BALANCE. PER 2004 FBC/R M1602.4 .
  
 7) UNIT 708 - 1/2 B, 12X6 RETURN AIR TRANSFER GRILL TO
 BEDROOM 1 IS UNDER SIZED, BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (B)TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO
 ACHIEVE PROPER RETURN AIR BALANCE. PER 2004 FBC/R
 M1602.4 .
  
 8) PLEASE ALSO SHOW SENSIBLE BTU'S IN A/C EQUIPMENT
 LISTING ON MECH. PLANS.
  
 9) PLEASE SUBMITMANUAL J CALCULATIONS, PER 2004 FBC
 13-607.1.ABC.1 .
  