Date |
Text |
2007-02-07 11:43:12 | *** DENIED *** |
| SEE MECHANICAL PLAN PAGE M-1. |
| |
| 1) UNIT 708 1ST. FL. BEDROOM 1, RETURN AIR TRANSFER |
| DUCT IS LISTED AS A RETURN AIR TRANSFER GRILL, PLEASE |
| CORRECT. |
| |
| 2) SAME UNIT PLEASE SHOW SIZE OF RETURN AIR TRANSFER |
| DUCT (FLEX). |
| |
| 3) UNIT 708 2ND. FL., ALL RETURN AIR TRANSFER DUCTS ARE |
| LISTED AS RETURN AIR TRANSFER GRILLS, PLEASE CORRECT. |
| |
| 4) SAME UNIT, PLEASE SHOW SIZE OF RETURN AIR TRANSFER |
| DUCTS (FLEX). |
| |
| 5) UNIT 708 -1/2 A,ALL RETURN AIR TRANSFER DUCTS ARE |
| LISTED AS RETURN AIR TRANSFER GRILLS, PLEASE CORRECT. |
| |
| 6) SAME UNIT, 7" RETURN AIR TRANSFER DUCTS (FLEX) ARE |
| UNDER SIZED FOR BEDROOMS, BALANCED RETURN AIR MAY BE |
| ACHIEVED BY. |
| (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE |
| RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS |
| SECTIONAL AREA |
| (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR |
| SPACE IT'S SERVING AND THE DOOR HAVING AT LEAST AN |
| UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE PROPER RETURN |
| AIR BALANCE. PER 2004 FBC/R M1602.4 . |
| |
| 7) UNIT 708 - 1/2 B, 12X6 RETURN AIR TRANSFER GRILL TO |
| BEDROOM 1 IS UNDER SIZED, BALANCED RETURN AIR MAY BE |
| ACHIEVED BY. |
| (B)TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF |
| GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING |
| THROUGH-THE-WALL TRANSFER GRILLES AND |
| USING AN UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO |
| ACHIEVE PROPER RETURN AIR BALANCE. PER 2004 FBC/R |
| M1602.4 . |
| |
| 8) PLEASE ALSO SHOW SENSIBLE BTU'S IN A/C EQUIPMENT |
| LISTING ON MECH. PLANS. |
| |
| 9) PLEASE SUBMITMANUAL J CALCULATIONS, PER 2004 FBC |
| 13-607.1.ABC.1 . |
| |
| MECHANICAL PLAN REVIEW BY; |
| TOM GORDON (561) 805-6729. |