2006-05-18 00:00:00 | |
| DENIED |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} THE SCOPE OF WORK ON THE APPLICATION |
| IS INTERIOR WALL RENOVATION. THE |
| ELECTRICAL SHEETS DO NOT INDICATE |
| EXISTING FROM NEW WORK. THEREFOR IT |
| WOULD APPEAR THE UNITS ARE TO BE |
| REWIRED. PLEASE INDICATE SAME ON THE |
| APPLICATION AND INCREASE VALUE TO |
| REFLECT SAME. IF SOME IS EXISTING AND |
| SOME IS NEW PLEASE INDICATE SAME AT THE |
| DEVICES. |
| |
| 2} THERE IS NO RECORD IN CITY HALL'S |
| FILES THAT WOULD INDICATE ELECTRICAL |
| UPGRADES. PLEASE PROVIDE LOAD |
| CALCULATIONS, PANEL SCHEDULES, AND THE |
| LOCATION OF ALL SERVICE EQUIPMENT, |
| INCLUDING METERS, DISCONNECT AND PANELS |
| PER 215.5. SEE 2002 NEC., 2004 |
| RESIDENTIAL BUILDING CODE, AND NFPA-72. |
| |
| 3} PLEASE SEE RECEPTALE SPACING AND |
| LOCATION REQUIREMENTS, NEC 2002, IF |
| REWIRING. SEE EXISTING BUILDING CHAPTERS |
| FOR INFORMATIION. |
| |
| COMPLY WITH THESE DOCUMENTS AND RESUBMIT |
| FOR REVIEW. |
| |
| "ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| NAME, ADDRESS, AND LICENSE NUMBER |
| ON EACH SHEET." 61G15-23.002 FAC. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |
| 561/805-6718 |