Plan Review Notes
Plan Review Notes For Permit 06030386
Permit Number 06030386
Review Stop M
Sequence Number 3
Notes
Date Text
2006-07-17 00:00:00*** DENIED ***
 1) DUCT LAY-OUT IS TO FADED ON
 MECHANICAL PLANS. CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY. PER 2004
 FBC 106.1.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved