Plan Review Notes For Permit 06030386 |
Permit Number |
06030386 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-05-26 00:00:00 | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 2} PLEASE LOCATE ALL SERVICE EQUIPMENT | | ON THE PLAN, METER ENCLOSURE, | | DISCONNECTS AND PANELS, SO THAT | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN | | BE REVIEWED. | | | | 3} PER 110.9 AND 110.10: OBTAIN THE | | AVAILABLE FAULT CURRENT AT THE UTILITY | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | INDICATE THE AIC RATING FOR THE | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | THE AVAILABLE FAULT. | | | | 4} INDICATE COMPLIANCE WITH ARTICLE | | 250.50 FOR THE GROUNDING ELECTRODE | | SYSTEM. ALL AVAILABLE MUST BE USED ON | | THE RISER. SIZE GEC PER 250.66. | | | | 5} THE GARAGE DOOR OPENER DOES NOT | | APPEAR ON THE PANEL SCHEDULE OR THE | | CALCULATIONS. | | | | 6} THE GARAGE RECEPTACLES MUST COMPLY | | WITH 210.8(A)(2), GFI. | | | | 7} 210.70(A)(1) HABITABLE ROOMS. AT | | LEAST ONE WALL SWITCH-CONTROLLED | | LIGHTING OUTLET SHALL BE INSTALLED IN | | EVERY HABITABLE ROOM AND BATHROOM. SEE | | LIVING ROOM. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | | | |
|