Date Text
2006-05-26 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON THE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN
 BE REVIEWED.
  
 3} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 4} INDICATE COMPLIANCE WITH ARTICLE
 250.50 FOR THE GROUNDING ELECTRODE
 SYSTEM. ALL AVAILABLE MUST BE USED ON
 THE RISER. SIZE GEC PER 250.66.
  
 5} THE GARAGE DOOR OPENER DOES NOT
 APPEAR ON THE PANEL SCHEDULE OR THE
 CALCULATIONS.
  
 6} THE GARAGE RECEPTACLES MUST COMPLY
 WITH 210.8(A)(2), GFI.
  
 7} 210.70(A)(1) HABITABLE ROOMS. AT
 LEAST ONE WALL SWITCH-CONTROLLED
 LIGHTING OUTLET SHALL BE INSTALLED IN
 EVERY HABITABLE ROOM AND BATHROOM. SEE
 LIVING ROOM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  