2006-03-16 00:00:00 | *********** UNSAT ************ |
| |
| 1)NOTE: PLEASE CORRELATE CIRCUITING, |
| CONDUCTOR SIZES, LOADS, FROM PANEL |
| SCHEDULE TO LOAD CALCULATIONS. |
| 215.5 |
| |
| 2)NOTE: PLEASE INCLUDE ALLMININUM |
| CONDUCTOR SIZES ON PANEL SCHEDULES. |
| PLEASE SEE THESE ARE SHOWN AS BLANK AT |
| THIS TIME. |
| PLEASE SEE NOTES PERTAINING TO THE SIZES |
| SHOWN ON LOAD CALCS, MANY ARE 15A |
| CIRCUITS W/ #12 AWG AND SOME ARE NOTA |
| LARGE ENOUGH FOR THE MIN REQ'D. |
| 215.5.310.16.240.4 |
| |
| 3)NOTE: PLEASE SEE MIN REQURIED DEDICATE |
| BATH (S) CIRCUITS PER 210.52D,210.11C3. |
| SHALL BE A MIN OF #12/ 20A. |
| |
| 4)NOTE: PLEASE SEE NUMEROUS SINGLE POLE |
| CIRCUITS WHICH ARE SHOWN AS 2-POLE |
| CIRCUITS ON PANEL SCHEDULE? PLEASE |
| CORRECT AND CORRELATE. |
| 215.5 |
| |
| 5)NOTE: PLEASE SEE CU SHOWS A DISCONNECT |
| AND A 220V RECEPT FOR CU?? |
| PLEASE CLARIFY WHAT THIS 22V RECEPT IS |
| FOR? |
| 440.11. |
| |
| 6)NOTE: PLEASE SEE WATER HEATER IS BEING |
| SHOWN WITH A RECEPT FOR UNIT. PLEASE SEE |
| 422.31 WHICH REQUIRES A DISCONNECT. |
| PLEASE SHOW. |
| |
| 7)NOTE: PLEASE CORRELATE RISER, PLANS, |
| AND PANEL SCHEDULE. |
| PLEASE SEE RISER SHOWS A FEED FROM THE |
| MCB PANEL TO ???? |
| PLEASE SEE PLANS DO NOT SHOW THE METER. |
| PLEASE SEE RISER NEEDS TO REFLECT |
| CONDUIT FROM METER TO MCB UNDERGROUND, |
| OR IF NOT UNDERGROUND, THEN A MAIN |
| DISCONNECT WITH OCP WILL BE REQUIRED |
| OUTSIDE. |
| 230.70,230.6 |
| PLEASE ALSO INDICATE THE AIC RATINGS FOR |
| ANY NEW DISCONNECTS. 110.9,215.5 |
| |
| 8)NOTE: PLEASE SEE "GFI" NOT E ON PLANS |
| WHICH MENTIONS ALL RECEPTS W/IN 15' FROM |
| POOL TO BE GFI. THIS IS NOT CORRECT, |
| PLEASE SEE 680.22 FOR MIN DISTANCE |
| REQUIRED. |
| |
| 9)NOTE: PLEASE SHOW AND LABEL ALL ROOM |
| AND AREA DESIGNATIONS ON ELECTRICAL |
| PLANS. |
| 215.5 |
| |
| 10)NOTE: PLEASE SEE BATH RM WHICH DOES |
| NOT SHOW THE SWITCH CONTROL TO THE LT/ |
| FAN. |
| 210.70 |
| |
| 11)NOTE: PLEASE SEE A RECEPT IN WHAT MAY |
| BE THE DINING ROOM, WHICH SHOWS THE |
| RECEPT BEING SWITCHED. PLEASE SEE |
| 210.52B1,210.70, THIS IS NOT PERMITTED |
| IN THE DINING AREA. THESE RECEPTS MUST |
| BE PART OF THE ONE OR MORE SMALL |
| APPLIANCE CIRCUITS. |
| PLEASE ADJUST. |
| |
| 12)NOTE: PLEASE SEE MISSING RECEPTS PER |
| 210.52 |
| |
| 13)NOTE: PLEASE SEE 210.8A2 FOR GARAGE |
| RECEPTS. |
| |
| 14)NOTE: PLEASE SEE KITCHEN PLANS |
| INDICATE TWO GFI RECEPTS UNDER KITCHEN |
| COUNTER? , IF THESE ARE FOR THE |
| DISHWASHER OR DIPOSAL, THESE WOULD BED |
| DEDICATED RECEPTS/ NON-GFI. |
| PLEASE SEE 210.52C1 AS KITCHEN COUNTER |
| SPACE MAY SEEM TO INDICATE COUNTER AT |
| POSSIBLY BEING OVER 4' WHICH WOULD |
| REQUIRE AN ADDTIONAL GFI RECEPT ON |
| COUNTER. |
| |
| 15)NOTE: PLEASE SEE MANY RMS CONTAIN |
| WHAT APPEARS TO BE A "J-BOX" , HOWEVER |
| PLEASE SEE THIS SYMBOL IS NOT SHOWN ON |
| SYMBOL SCHEDULE FOR USE/PURPOSE. |
| |
| 16)NOTE: PLEASE SEE THAT PLANS ARE |
| REQUIRED TO CONTAIN THE PRINTED NAME AND |
| SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| PLANS. |
| |
| PLEASE SEE ANY OTHER COMMENTS FROM OTHER |
| REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| PLANS.471,481,489 ETC |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |