Plan Review Notes
Plan Review Notes For Permit 06030386
Permit Number 06030386
Review Stop E
Sequence Number 1
Notes
Date Text
2006-03-16 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE CORRELATE CIRCUITING,
 CONDUCTOR SIZES, LOADS, FROM PANEL
 SCHEDULE TO LOAD CALCULATIONS.
 215.5
  
 2)NOTE: PLEASE INCLUDE ALLMININUM
 CONDUCTOR SIZES ON PANEL SCHEDULES.
 PLEASE SEE THESE ARE SHOWN AS BLANK AT
 THIS TIME.
 PLEASE SEE NOTES PERTAINING TO THE SIZES
 SHOWN ON LOAD CALCS, MANY ARE 15A
 CIRCUITS W/ #12 AWG AND SOME ARE NOTA
 LARGE ENOUGH FOR THE MIN REQ'D.
 215.5.310.16.240.4
  
 3)NOTE: PLEASE SEE MIN REQURIED DEDICATE
 BATH (S) CIRCUITS PER 210.52D,210.11C3.
 SHALL BE A MIN OF #12/ 20A.
  
 4)NOTE: PLEASE SEE NUMEROUS SINGLE POLE
 CIRCUITS WHICH ARE SHOWN AS 2-POLE
 CIRCUITS ON PANEL SCHEDULE? PLEASE
 CORRECT AND CORRELATE.
 215.5
  
 5)NOTE: PLEASE SEE CU SHOWS A DISCONNECT
 AND A 220V RECEPT FOR CU??
 PLEASE CLARIFY WHAT THIS 22V RECEPT IS
 FOR?
 440.11.
  
 6)NOTE: PLEASE SEE WATER HEATER IS BEING
 SHOWN WITH A RECEPT FOR UNIT. PLEASE SEE
 422.31 WHICH REQUIRES A DISCONNECT.
 PLEASE SHOW.
  
 7)NOTE: PLEASE CORRELATE RISER, PLANS,
 AND PANEL SCHEDULE.
 PLEASE SEE RISER SHOWS A FEED FROM THE
 MCB PANEL TO ????
 PLEASE SEE PLANS DO NOT SHOW THE METER.
 PLEASE SEE RISER NEEDS TO REFLECT
 CONDUIT FROM METER TO MCB UNDERGROUND,
 OR IF NOT UNDERGROUND, THEN A MAIN
 DISCONNECT WITH OCP WILL BE REQUIRED
 OUTSIDE.
 230.70,230.6
 PLEASE ALSO INDICATE THE AIC RATINGS FOR
 ANY NEW DISCONNECTS. 110.9,215.5
  
 8)NOTE: PLEASE SEE "GFI" NOT E ON PLANS
 WHICH MENTIONS ALL RECEPTS W/IN 15' FROM
 POOL TO BE GFI. THIS IS NOT CORRECT,
 PLEASE SEE 680.22 FOR MIN DISTANCE
 REQUIRED.
  
 9)NOTE: PLEASE SHOW AND LABEL ALL ROOM
 AND AREA DESIGNATIONS ON ELECTRICAL
 PLANS.
 215.5
  
 10)NOTE: PLEASE SEE BATH RM WHICH DOES
 NOT SHOW THE SWITCH CONTROL TO THE LT/
 FAN.
 210.70
  
 11)NOTE: PLEASE SEE A RECEPT IN WHAT MAY
 BE THE DINING ROOM, WHICH SHOWS THE
 RECEPT BEING SWITCHED. PLEASE SEE
 210.52B1,210.70, THIS IS NOT PERMITTED
 IN THE DINING AREA. THESE RECEPTS MUST
 BE PART OF THE ONE OR MORE SMALL
 APPLIANCE CIRCUITS.
 PLEASE ADJUST.
  
 12)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52
  
 13)NOTE: PLEASE SEE 210.8A2 FOR GARAGE
 RECEPTS.
  
 14)NOTE: PLEASE SEE KITCHEN PLANS
 INDICATE TWO GFI RECEPTS UNDER KITCHEN
 COUNTER? , IF THESE ARE FOR THE
 DISHWASHER OR DIPOSAL, THESE WOULD BED
 DEDICATED RECEPTS/ NON-GFI.
 PLEASE SEE 210.52C1 AS KITCHEN COUNTER
 SPACE MAY SEEM TO INDICATE COUNTER AT
 POSSIBLY BEING OVER 4' WHICH WOULD
 REQUIRE AN ADDTIONAL GFI RECEPT ON
 COUNTER.
  
 15)NOTE: PLEASE SEE MANY RMS CONTAIN
 WHAT APPEARS TO BE A "J-BOX" , HOWEVER
 PLEASE SEE THIS SYMBOL IS NOT SHOWN ON
 SYMBOL SCHEDULE FOR USE/PURPOSE.
  
 16)NOTE: PLEASE SEE THAT PLANS ARE
 REQUIRED TO CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 PLANS.
  
 PLEASE SEE ANY OTHER COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.471,481,489 ETC
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  