2006-04-07 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- NEED RECORDED NOC. |
| |
| 2- A) SURVEY WAS PREPARED FOR MORTGAGE |
| ONLY, IT CAN'T BE USED FOR PERMITTING. |
| SEE GENERAL NOTE #12. NEED SURVEY FOR |
| PERMITTING PURPOSES. |
| B) SURVEY TO HAVE ORIGINAL SIGNATURE |
| AS REQUIRED BY CHAPTER 472 FL. STATUTE. |
| |
| 3- PROVIDE DRAINAGE PLAN AS REQUIRED BY |
| SEC. R401.3 OF 2004 RESIDENTIAL CODE. |
| |
| 4- SHEET A-1: A) CLARIFY EXTERIOR |
| ELEVATIONS. ROOF PITCH IS DRAWN TO 6:12, |
| WHILE WRITTEN PITCH CALLS FOR 4:12. |
| REVISE AS REQ'D. |
| B) SQUARE FOOTAGES DON'T MATCH ACTUAL |
| SQUARE FOOTAGES SHOWN ON FLOOR PLAN. |
| REVISE SQUARE FOOTAGE AREAS AND TOTAL |
| SQUARE FOOTAGE TO MATCH 1ST FL PLAN. |
| PROJECT VALUATION WILL BE CALCULATED |
| AFTER CORRECT SQUARE FOOTAGE IS PROVIDED |
| AND ADDITIONAL FEES MAY BE DUE. |
| C) REVISE TOP OF LINTEL ELEVATION. |
| 8'-0" HIGH DOORS DON'T FIT IF TOP OF |
| LINTEL IS AT 8'-0". |
| D) CLARIFY WHAT'S THE BLACK SOLID |
| LINE SHOWN ON ARCHED WINDOW BETWEEN |
| SINGLE HUNG WINDOW & ARCHED WINDOW. |
| |
| 5- SHEET A-2: A) FOUNDATION PLAN AND |
| FIRST FLOOR PLAN ARE MISSING STEP AT |
| ENTRY PORCH, GARAGE SIDE DOOR AND REAR |
| SLIDING GLASS DOORS. |
| B) CLARIFY IF WATER HEATER AND A/C |
| ARE LOCATED ON AN ELEVATED AREA FROM |
| GARAGE FINISH FLOOR.IF SO, FOOTING |
| DOESN'T MATCH. REVISE AS REQUIRED. |
| C) SPECIFY ATTIC LOCATION AND SIZE. |
| SEC. R807 2004 RESIDENTIAL CODE. |
| D) SPECIFY CONCRETE SLAB CONTROL |
| JOINTS OR WWM SUPPORTS AND SPACING AS |
| REQ'D BY SEC. R506.2.4 2004 RESIDENTIAL |
| CODE EXCEPTION #2. |
| E) PROVIDE BATHROOM WITH DOOR THAT |
| ALLOWS 29" MIN. CLEAR OPENING. SEC. R322 |
| 2004 RESIDENTIAL CODE. |
| F) SPECIFY TYPE OF GARAGE DOOR AS |
| REQUIRED BY SEC. R309.12004 RES. CODE. |
| G) ARCH FRAME DETAIL: SPECIFY HOW LONG |
| ARE THE 1/2" WEDGE ANCHORS AND CLARIFY |
| FASTENER FOR DIAGONAL BAR. SEE COMMENTS |
| ON PLAN. SEC. 106.1.2CITY AMENDMENTS |
| TO FBC 2004. |
| |
| 6- SHEET A-3: REVISE TRUSS ANCHOR |
| SCHEDULE. NUMBER OF FASTENERS AND LOADS |
| SPECIFIED FOR HLPTA-75 DON'T MATCH USP |
| CATALOGUE. SEE CURRENT CATALOGUE AND |
| PRODUCT APPROVAL. REVISE AS REQUIRED. |
| |
| 7- SHEET D-1:TYPICAL 1 STORY SECTION: |
| A) REVISE EAVE DETAIL. DRAWN |
| INCORRECTLY. NEED TO SHOW TRUSS LEG. |
| B) SPECIFY ROOF VENTILATION AS REQ'D |
| BY SEC. R806 2004 RESIDENTIAL CODE. |
| C) WHAT'S SBXR-30? |
| D) WINDOW SILL SHOWN DOESN'T MATCH |
| SPECIFICATIONS. |
| E) SPECIFICATIONS FOR ROOF SHEATHING |
| DON'T MATCH THOSE SHOWN IN THE ROOF/WALL |
| SHEATHING TABLE ON SAME PAGE. REVISE AS |
| REQUIRED. |
| F) WHERE IS THE UPLIFT TABLE FOR |
| REBAR SPACING? |
| |
| 8- REVISE ALL GENERAL NOTES ON SHEET |
| D-1. SEE CHAPTER 43 OF 2004 RESIDENTIAL |
| CODE FOR ADOPTED STANDARDS AND EDITIONS |
| TO BE USED. |
| |
| 9- PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL FOR: |
| A) ARCHED FIXED WINDOW. NEED 2004 |
| FLORIDA CODE VERSION AND DRAWINGS WERE |
| NOT SUBMITTED IN THIS PACKAGE. |
| B) GARAGE SIDE DOOR. |
| C) ENTRY DOOR. NEED 2004 FLORIDA CODE |
| VERSION AND DRAWINGS ARE MISSING TOO. |
| ***NOTE: ENGINEER OF RECORD TO REVIEW |
| AND APPROVE ABOVE MENTIONED PRODUCT |
| APPROVALS PRIOR TO SUBMITTAL. |
| |
| 10-STORM SHUTTERS: A) NEED 2004 FLORIDA |
| CODE VERSION. |
| B) DADE COUNTY NOA #03-0421.12 WAS |
| SUPERSEDED. SEE DADE COUNTY WEBSITE. |
| C) PROVIDE KEY PLAN AND COMPLETE |
| INSTALLATION SCHEDULE. SEE ATTACHED |
| SAMPLE WHICH PROVIDES ALL REQUIRED |
| INFORMATION FOR PLAN REVIEW. |
| D) ENGINEER OF RECORD TO REVIEW |
| PRODUCT APPROVAL AS REQUIRED BY SEC. |
| 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| |
| 11- A) SOIL TEST REPORT WAS ADDRESSED TO |
| PALM BEACH COUNTY. PROPERTY IS LOCATED |
| IN THE CITY OF WEST PALM BEACH. REVISE |
| AS REQUIRED. |
| B) SEE 2004 RESIDENTIAL CODE FOR |
| CORRECT CODE SECTION TO BE REFERENCED. |
| AND REVISE AS REQUIRED. |
| C) THERE WERE NOT ATTACHMENTS |
| SUBMITTED IN THIS PACKAGE. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |