2006-03-17 00:00:00 | *** UNSAT *** |
| |
| 1)NOTE: PLEASE SEE EXISTING PANEL |
| INDICATES AHU'S #1 AND #2 AS 10KW UNITS |
| WITH 1-POLE OCP?? PLEASE KNOW, EVEN IF |
| THIS SI EXISITNG? THIS WILL BE REQUIRED |
| TO BE BROUGHT UP TO CODE AS IT VIOLATE'S |
| MANY NEC ARTICLES AND PROMOTES A LIFE |
| SAFETY AND PROPERTY HAZARD. |
| 240.4,424.3,310.16 ETC ETC. |
| |
| 2)NOTE: PELASE SEE FBC 2004 CHAPTER 13, |
| FOR COMMERCIAL BLDGS. 13-415.1.ABC.1.1 |
| &.2,13-415.1.ABC.3 PROVIDE DETAILED |
| INFORMATION ON TYOE OF LT FIXTURES. |
| PLEASE SEE THE NEW REQUIREMENTS FOR THE |
| NEW ENERGY CODE. |
| |
| 3)NOTE: PLEASE MAKE REFERENCE TO 605, |
| 605.6 ON PLANS FOR INSTALLATIONS OF |
| FURNITURE. |
| |
| 4)NOTE: PLEASE SEE PLANS SHALL DICTATE |
| THE CURRENT CODES IN EFFECT. 2002 |
| NFPA-70, 2003 NFPA-101,2002 NFPA-72. |
| |
| ** PLEASE BE SURE TO REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| REVISED SHEETS INTO TWO COMPLETE SETS |
| FOR REVIEW AND STAMPING. |
| ONLY ONE COPY OF THE REMOVED OLD/VOIDED |
| SHEETS SHOULD BE SUBMITTED FOR |
| REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |