Plan Review Notes For Permit 06030268 |
Permit Number |
06030268 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-04-18 00:00:00 | | | FAILED | | SAME NOTES AS PREVIOUS REVIEW (3.20.06), | | PLEASE SEE THAT MR SINCLAIR GETS AN | | OPPORTUNITY TO SEE THE COMMENTS BEFORE | | RESUBMITTING | | | | THE PLAN INDICATES 3-#4 CU FEEDERS TO | | THE POOL PANEL. THE CALCULATION PROVIDED | | BYTHE ELECTRICAL CONTRACTOR INDICATES A | | 30 AMP FEED TO A POOL PANEL. PLEASE | | CORRELATE. | | | | NOTE #1 AT THE ELECTRICAL SCHEMATIC | | REFERENCES THE 2005 NEC. PLEASE NOTE THE | | STATE HAS NOT YET ADOPTED 2005 AND WE | | ARE CURRENTLY ENFORCING 2002 NEC. | | | | DIFFERENTCOMMENT FROM THIS REVIEW, | | THERE IS A HEATER (PRESUMABLY ELECTRIC) | | ON THE ELECTRICAL SCHEMATIC THAT SHOULD | | BE REMOVED . IF THE HEATER IS GAS THERE | | SHOULD ONLY BE AN IGNITOR INDICATED IF | | 120V. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|