Plan Review Notes
Plan Review Notes For Permit 06030268
Permit Number 06030268
Review Stop E
Sequence Number 1
Notes
Date Text
2006-03-20 00:00:00 
 FAILED
  
 THE PLAN INDICATES 3-#4 CU FEDERS TO THE
 POOL PANEL. THE CALCULATION PROVIDED BY
 THE ELECTRICAL CONTRACTOR INDICATES A 30
 AMP FEEDTO A POOL PANEL. PLEASE
 CORRELATE.
  
 NOTE #1 AT THE ELECTRICAL SCHEMATIC
 REFERENCES THE 2005 NEC. PLEASE NOTE THE
 STATE HAS NOT YET ADOPTED 2005 AND WE
 ARE CURRENTLY ENFORCING 2002 NEC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW