2006-03-20 00:00:00 | | | FAILED | | | | THE PLAN INDICATES 3-#4 CU FEDERS TO THE | | POOL PANEL. THE CALCULATION PROVIDED BY | | THE ELECTRICAL CONTRACTOR INDICATES A 30 | | AMP FEEDTO A POOL PANEL. PLEASE | | CORRELATE. | | | | NOTE #1 AT THE ELECTRICAL SCHEMATIC | | REFERENCES THE 2005 NEC. PLEASE NOTE THE | | STATE HAS NOT YET ADOPTED 2005 AND WE | | ARE CURRENTLY ENFORCING 2002 NEC. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | |
|