Plan Review Notes
Plan Review Notes For Permit 06030245
Permit Number 06030245
Review Stop M
Sequence Number 2
Notes
Date Text
2006-10-11 11:39:13*** MECHANICAL REVISION DENIED ***
 1) MANUAL J CAL'S ON FILE ARE CALLING FOR A/C #3 TO BE
 24,332 SENSIBLE BTU'S
 PLANS ARE CALLING FOR A/C #3 TO BE 31,700 SENSIBLE
 BTU'S. THE PLANS CAN ONLY
 CALL FOR 20% MORE THEN THE MANUAL J CAL'S, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  