Plan Review Notes For Permit 06030245 |
Permit Number |
06030245 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-04-06 00:00:00 | BUILDING REVIEW PROVISO: | | **1- STORM SHUTTERS ON SEPARATE PERMIT. | | | | **2- RE-SUBMIT SURVEY WITH ORIGINAL | | SIGNATURE AS REQ'D BY CHAPTER 472 FL ST | | | | **3- PROVIDE DRAINAGE PLANS AS REQ'D BY | | SEC. R401.3 2004 RESIDENTIAL CODE. | | | | **4- PROVIDE FLORIDA OR LOCAL PRODUCT | | APPROVAL FOR: | | A) CASEMENT IMPACT WINDOW. SEE PLANS. | | B) FRENCH DOORS. NEED SAME NOA THAT WAS | | SUBMITTED FOR FLORIDA APPROVAL. | | SEE WEBSITE TO DOWNLOAD SPECIFIC NOA. | | WWW.FLORIDABUILDING.ORG. | | C) ENTRY DOORS. INFORMATION SUBMITTED | | SAYS "PENDING FBC APPROVAL". NEED | | PRODUCT APPROVAL WITH APPROVED STATUS. | | D) SINGLE HUNG WINDOWS. NEED COPY OF | | SAME NOA SUBMITTED FOR FLORIDA APPROVAL. | | E) 2" MULLION. NEED COPY OF SAME NOA | | SUBMITTED FOR FLORIDA APPROVAL. | | F) 1" MULLION. NEED COPY OF SAME NOA | | SUBMITTED FOR FLORIDA APPROVAL. | | | | ***REMAINDER: MAKE SURE DESIGNER OF | | RECORD REVIEWS ALL PRODUCT APPROVALS | | PRIOR TO SUBMITTAL TO THIS OFFICE. |
|