2006-05-17 00:00:00 
  
 **************REVISION***************
  
 DENIED
  
 1) AN ENGINEER PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS SHALL
 INDICATE THEIR NAME AND LICENCE #, AS
 WELL AS THE NAME,ADDRESS AND CERTIFICATE
 OF AUTHORIZATION #ON EACH SHEET PER
 61G15-23.002 (2) FAC
  
 2) PLYWOOD ATTACHMENT DOES NOT MEET THE
 MINIMUM REQUIREMENTS AS SET FORTH IN
 TABLE 2304.9.1 FBC
  
 3) FASTENER SPACING FOR ZONE 1 SHALL NOT
 BE LESS THAN SPECIFIED IN THE NOA. THE
 ENHANCEMENT OF FASTENERS IS ONLY
 REQUIRED FOR ZONE 2 PERIMETER AND ZONE 3
 CORNER
  
 4) RAS117 10.4.5, ALL FRACTIONS ARE TO
 ROUNDED DOWN TO THE NEXT WHOLE NUMBER.
  
 5) THE FASTENING PATTERN SHOWN
 GRAPHICALLY ON THE RAS 117 CALCULATIONS
 ARE NOT CORRECT.IF YOU DO NOT UNDERSTAND
 THIS, SEE RAS117 AND THE EXAMPLE
 CALCULATION IN REGARDS TO DETERMINING
 HOW MANY FASTENERS PER SQUARE.
  
 6) THE SIGNATURES APPEAR TO BE A
 PHOTOCOPY. ORIGINAL WET SIGNATURE
 REQUIRED PER FBPE.
  
 7) INITIALS ARE NOT ACCEPTABLE AS A
 SIGNATURE PER FBPE.
  
  