Plan Review Notes
Plan Review Notes For Permit 06030193
Permit Number 06030193
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-03-09 00:00:00DENIED:
  
 1) SHALL COMPLY WITH NFPA 101 LIFE
 SAFETY CODE, 2003 EDITION, AND NFPA 1
 UNIFORM FIRE CODE, 2003.
  
 2) SINCE THIS BUILDING WILL BE OCCUPLIED
 WHILE THE DEMOLITION, RENOVATION, AND
 CONSTRUCTION ARE GOING ON, IT'S SHALL
 COMPLY NFPA 241.
  
 3) PLEASE PROVIDE A SEATING LAYOUT OF
 THE DINING ROOM, ON THE FLOOR PLAN FOR
 APPROVAL BY THIS OFFICE.
  
 4) IS THE TENANT SEPARATION ONE HOUR
 RATED ON BOTH SIDE OF THIS PROJECT.
  
 5) THE REAR EXIT DOOR APPEARS TO BE
 OBSTRUCTED BY THE OFFICE AND RESTROOM
 DOORS.
  
 6) INTERIOR WALLS AND CEILING FINISH
 MATERIALS COMPLYING WITH SECTION 10.2
 SHALL BE CLASS A THROUGHOUT.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754