2006-03-27 00:00:00 | DENIED |
| |
| 1) PLANS SPECIFY THE EXISTING BUILDING |
| TYPE AS TYPE IIA, UNPROTECTED. ACCORDING |
| TO 2004 FBC TABLE 601 A TYPE IIA |
| BUILDING IS ESSENTIALLY ONE HOUR |
| PROTECTED. PLEASE CLARIFY. IS THE SPACE |
| FIRE SPRINKLERED? |
| |
| 2) THE SCOPE OF WORK IS TO OPEN THE WALL |
| BETWEEN TWO TENANT SPACES CREATING ONE |
| LARGE SPACE. PROVIDE A DRAWING OF THE |
| EXISTING SPACE WITH THE DIMENSIONS AND |
| OCCUPANT LOADS FOR THE COMBINED SPACES. |
| INDICATE THE EXISTS AND PATHS OF TRAVEL |
| FOR THE COMBINED SPACE. |
| |
| 3) SPECIFY ON PLANS THAT THE ALTERATIONS |
| TO THE PRIMARY FUNCTION AREA COMPLY WITH |
| FLORIDA ACCESIBILITY CODE AS REQUIRED BY |
| 2004 FBC 11-4.1.6. |
| |
| 11-4.1.6(2) DUTY TO PROVIDE AN |
| ACCESSIBLE PATH OF TRAVEL TO ALTERED |
| AREAS SHALL BE DEEMED DISPROPORTIONATE |
| TO THE OVERALL ALTERATION WHEN THE COST |
| EXCEEDS 20 % OF THE COST OF THE ALTERA- |
| TION TO THE PRIMARY FUNCTION AREA. |
| (A)(I) AN ACCESSIBLE ENTRANCE |
| (II) AN ACCESSIBLE ROUTE |
| (III) AT LEAST ONE ACCESSIBLE REST- |
| ROOM FOR EACH SEX OR A SINGLE |
| UNISEX RESTROOM |
| (IIII) ACCESSIBLE TELEPHONE |
| (IV) ELEMENTS SUCH AS PARKING, STOR- |
| AGE OR ALARMS. |
| |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| |