Plan Review Notes
Plan Review Notes For Permit 06030193
Permit Number 06030193
Review Stop B
Sequence Number 1
Notes
Date Text
2006-03-27 00:00:00DENIED
  
 1) PLANS SPECIFY THE EXISTING BUILDING
 TYPE AS TYPE IIA, UNPROTECTED. ACCORDING
 TO 2004 FBC TABLE 601 A TYPE IIA
 BUILDING IS ESSENTIALLY ONE HOUR
 PROTECTED. PLEASE CLARIFY. IS THE SPACE
 FIRE SPRINKLERED?
  
 2) THE SCOPE OF WORK IS TO OPEN THE WALL
 BETWEEN TWO TENANT SPACES CREATING ONE
 LARGE SPACE. PROVIDE A DRAWING OF THE
 EXISTING SPACE WITH THE DIMENSIONS AND
 OCCUPANT LOADS FOR THE COMBINED SPACES.
 INDICATE THE EXISTS AND PATHS OF TRAVEL
 FOR THE COMBINED SPACE.
  
 3) SPECIFY ON PLANS THAT THE ALTERATIONS
 TO THE PRIMARY FUNCTION AREA COMPLY WITH
 FLORIDA ACCESIBILITY CODE AS REQUIRED BY
 2004 FBC 11-4.1.6.
  
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  