Plan Review Notes For Permit 06030168 |
Permit Number |
06030168 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-03-22 00:00:00 | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE SUBMIT A RISER DIAGRAM AND | | PANL SCHEDULES FOFR ALL PANELS. | | | | 2} THE "POOL HOUSE" MUST COMPLY WITH | | 225.31 DISCONNECTING MEANS AND 250.32 | | GROUNDING. SHOW SAME ON RISER. | | | | 3} SHOW LOCATION OF THE SERVICE | | EQUIPMENT. | | | | 4} THE KITCHEN COUNTERTOP RECEPTACLES | | MUST COMPLY WITH 210.8(A)(6). GFI. | | | | 5} THE BATH RECEPTACLES MUST COMPLY WITH | | 210.8(A)(1) | | | | 6} THE MASTER BATH MUST COMPLY WITH | | BASIN RECEPTACLE SPACING. SEE 210.52(D). | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|