2006-03-22 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT A RISER DIAGRAM AND
 PANL SCHEDULES FOFR ALL PANELS.
  
 2} THE "POOL HOUSE" MUST COMPLY WITH
 225.31 DISCONNECTING MEANS AND 250.32
 GROUNDING. SHOW SAME ON RISER.
  
 3} SHOW LOCATION OF THE SERVICE
 EQUIPMENT.
  
 4} THE KITCHEN COUNTERTOP RECEPTACLES
 MUST COMPLY WITH 210.8(A)(6). GFI.
  
 5} THE BATH RECEPTACLES MUST COMPLY WITH
 210.8(A)(1)
  
 6} THE MASTER BATH MUST COMPLY WITH
 BASIN RECEPTACLE SPACING. SEE 210.52(D).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW