Plan Review Notes For Permit 06030124
Permit Number 06030124
Review Stop M
Sequence Number 1
Notes
Date Text
2006-03-07 00:00:00*** DENIED ***
 1) ENERGY CALAULATIONS SUBMITTED WITH
 BUILDING PERMIT IS CALLING FOR 28,000
 TOTAL BTU'S, PLANS SUBMITTED ARE CALLING
 FOR 31,200 TOTAL BTU'S. THE PLANS CAN
 NOT CALL FOR MORE THAN THE ENERGY CAL'S.
 PLEASE CORRECT.
  
 2) PLANS ARE CALLING FOR MORE SENSIBLE
 BTU'S THAN THE MANUAL J CAL. WILL ALLOW
 PLEASE CORRECT.
  
 3) PLEASE SHOW THE COPPER LINE SIZES,
 AND THE CONDENSATE DRAIN LINE LOCATION
 ON THE MECHANICAL PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  