2006-08-03 00:00:00 | ******DENIED 3RD TIME****** |
| REFERENCE: FBC-2004 PLUMBING |
| |
| THE FOLLOWING INFORMATION IS STILL |
| REQUIRED FOR PLUMBING PLAN REVIEW: |
| |
| 1. PER FBC-2004, PLUMBING, SECTION 909.1 |
| WET VENT PERMITTED: ONLY THE FIXTURES |
| WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| TO THE WET-VENTED HORIZONTAL BRANCH |
| DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| DISCHARGE DOWNSTREAM OF THE WET VENT. |
| PLEASE SEE CORECTED DRAWING OF KITCHEN |
| SINK. |
| 2. PER FBC-2004,PLUMBING, SECTION 905.3 |
| VENT CONNECTIONS TO DRAINAGE SYSTEM. |
| EVERY DRY VENT CONNECTING TO A |
| HORIZONTAL DRAIN SHALL CONNECT ABOVE THE |
| CENTERLINE OF THE HORIZONTAL DRAIN PIPE. |
| PLEASE SEE CORRECTED DRAWING OF 3" |
| HORIZONTAL VENT BRANCH DOWNSTREAM OF THE |
| W.C. |
| 3. PER FBC-2004 PLUMBING, SECTION |
| 901.2.1 VENTING REQUIRED: EVERY TRAP AND |
| TRAPPED FIXTURE SHALL BE VENTED IN |
| ACCORDANCE WITH ONE OF THE VENTING |
| METHODS SPECIFIED IN THIS CHAPTER. |
| PLEASE SEE WHERE THE HORIZONTAL BRANCH |
| TO THE BATH LAV. MOVED ABOVE THE TUB. |
| 4. PER FBC-2004 PLUMBING, SECTION 708.7, |
| EXCEPTION 1, CLEANOUT NOT REQUIRED ON |
| KITCHEN SINK DUE TO THE FACT TRAP IS NOT |
| MORE THAN ONE PIPE SIZE SMALLLER THAN |
| THE DRAIN SERVED. PLEASE SEE CORRECTED |
| DRAWING WHERE CLEANOUT INDICATED ON |
| KITCHEN SINK P-TRAP. |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. (NOTE: PLEASE SEE CORRECTED |
| DRAWING IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL, ONLY ONE CORRECTED DRAWING |
| IN RED INK) |
| |
| END OF COMMENTS: |
| |