2006-06-05 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED FROM PLUMBING PLAN REVIEW:
  
 1. PER CHAPTER 1, SECTION 106:
 MORE INFORMATION REQUIRED. PLEASE
 INDICATE ON DRAWING EXISTING PLUMBING
 LAYOUT, AND ON A SEPERATE DRAWING
 INDICATE ON THE DRAWING THE NEW PROPOSED
 PLUMBING LAYOUT. IF NEW PROPOSED
 PLUMBING LAYOUT IS DIFFERENT FROM
 EXISTING PLEASE FOLLOW WHAT IS REQUIRED
 IN #2. IF PLUMBING LAYOUT IS THE SAME
 WITH NO CHANGES, PLEASE INDICATE THIS ON
 THE DRAWING. IF PLUMBING LAYOUT IS THE
 SAME AND THE PLUMBING FIXTURES ARE TO BE
 CHANGED, PLEASE INDCATE ON DRAWING
 FIXTURE CHANGE OUT ONLY.
 2. 106.3.5.4 RESIDENTIAL (ONE AND TWO
 FAMILY) SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM INDICATING ALL
 WASTE, VENTS, TRAPS WITH SIZES, AND
 CLEANOUT LOCATIONS.(NOTE: PLEASE SEE
 CORRECTED DRAWING IN RED INK FOR
 REFERENCE FOR RESUBMITTAL)
 3. THE FOLLOWING IS REQUIRED FOR CLEAN-
 OUT LOCATIONS PLEASE SEE CORRECTED
 DRAWING IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
 (A) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK(NOTE: SEE CORRECTED
 DRAWING IN RED INK FOR REFERENCE FOR
 RESUBMITTAL)
 (B) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 (NOTE: SEE CORRECTED DRAWING IN RED INK
 FOR REFERENCE FOR RESUBMITTAL)
 (C) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.(NOTE: SEE
 LOCATION OF WASHING MACHINE CLEANOUT
 LOCATION IN RED INK OF CORRECTED DRAWING
 FOR REFERENCE FOR RESUBMITTAL)
 4. CHANGE S.V. ON KITCHEN SINK TO
 AUTOMATIC AIR VENT (A.A.V.) SEE
 CORRECTED DRAWING IN RED INK FOR
 REFERENCE FOR RESUBMITTAL.
 5. THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK OF THE PLUMBING ISOMETRIC
 RISER DIAGARAM. TWO RESUBMITTED DRAWINGS
 OF THE ISOMETRIC PLUMBING RISER DIAGRAM
 INDICATING THE ABOVE CORRECTIONS AND
 THOSE CORRECTIONS INDICATED ON THE
 CORRECTED RISER DIAGRAM ARE REQUIRED FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  