Plan Review Notes For Permit 06030074 |
Permit Number |
06030074 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-05-26 00:00:00 | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PANEL SCHEDULE AND LOAD CALCULATIONS | | FOR "B" ARE INCOMPLETE. THERE IS A | | KITCHEN, 220.16"A", A BATHROOM, | | 210.11(C)(3)., MICROWAVE, STOVE OR | | REFRIGERATOR LISTED. | | | | 2} THE KITCHEN DOES NOT APPEAR TO HAVE | | THE REQUIRED NUMBER OF RECEPTACLES PER | | 210.52(C). NOTE THE SCALE ON PLANS. DRAW | | TO SCALE PER FBC ADMIN CODE, CHAPTER 1. | | | | 3} THE SMOKE DETECTOR IN THE KITCHEN | | MUST BE 3" FRROM THE DOOR, 20" FROM THE | | RANGE, OR BE HEAT SENSING TYPE. NFPA-72. | | | | 4} GFI'S ARE MISSING IN THE BATHROOM, | | 210.8(A)(1), GARAGE 210.8(A)(2), AND | | KITCHEN, 210.8(A)(6). | | | | THE PERSON TAKING RESPONSIBILITY FOR THE | | DESIGN MUST PRINT AND SIGN THEIR NAME TO | | SAME PER 106.3.4.2. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|