Notes
Date Text
2006-03-27 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)CALCULATIONS REQUIRED, SEE NOA
 PRODUCT LIMITATION #7.THE ENGINEERING
 DOCUMENT SUBMITTED IS A SPECIFICATION.
 CALCULATIONS IN ACCORDANCE WITH RAS117
 ARE REQUIRED.
  
 2.)TWO COPIES OF ALL PERMIT DOCUMENTS
 REQUIRED.ONLY ONE LETTER FROM THE
 ENGINEER WAS SUBMITTED.
  
 3.)PRIOR TO RESUBMITTING, PICK UP THE
 DENIED PACKAGE AND INCLUDE THIS
 DOCUMENTATION IN YOUR RESUBMITTAL.YOUR
 APPLICATION, NOC, AND OTHER REQUIRED
 DOCUMENTS WERE IN THE DENIED PACKAGE
 WHICH WAS STILL AT THE FRONT COUNTER
 WHEN YOU RESUBMITTED.THE TWO PACKAGES
 (DENIED PACKAGE, NEW PAPERWORK) MUST BE
 COMBINED PRIOR TO RESUBMITTAL.