Plan Review Notes
Plan Review Notes For Permit 06021135
Permit Number 06021135
Review Stop M
Sequence Number 7
Notes
Date Text
2007-04-25 16:22:24REVISION TO ENERGY CAL'S.
 *** DENIED ***
 1) REVISED COOLING LOAD CALCULATIONS SHOW THAT THE A/C
 SYSTEMS ON THE MECHANICAL PLANS ARE TO LARGE, SEE 2001
 FBC 13-607.1.ABC.1.1, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.